Installation: Piping
GLND-SVX01B-EN 21
The following instructions apply to Canadian installations
in addition to installation and operating instructions:
1. Installation must conform with local building codes, or
in absence of local codes, with current CSA B149.1,
“Installation Codes for Natural Gas Burning
Appliances and Equipment”, or CSA B149.2,
“Installation Codes for Propane Gas Burning
Appliances and Equipment”.
2. Any references to U.S. standards or codes in these
instructions are to be ignored and the applicable
Canadian standards or codes applied.
3. If using a metal vent system under positive gauge
pr
essure in Canada, a slip fit vent connection must be
secured by at least two corrosion-resistant screws, or
other mechanical locking means.
4. The vent shall not terminate:
a. Less than six feet (1.8 m) from a combustion air inlet
or another appliance.
b. Less than three feet (1 m) from any other building
opening or any gas service regulator.
c. Directly above a gas utility meter or service
regulator.
Figure 12. Adaptor installation
Refer to specification table and installation manual for proper usage.
Note: USA units—The reducer must be field supplied for 100, 125,
150, and 175 MBh unit sizes.