Installation: Mechanical
When the unit is equipped with an automatic gas ignition
system, the duct furnaces must be installed such that the
gas ignition control system is not directly exposed to water
spray, rain, or dripping water.
Note: Location of duct furnaces is related directly to the
selection of sizes. Basic rules are as follows:
Aircraft Hangers. Duct furnaces must be installed in
aircraft hangars and public garages as follows: in aircraft
hangars, duct furnaces must be at least 10 feet (3.0 m)
above the upper surface of wings or engine enclosures of
the highest aircraft to be stored in the hangar, and 8 feet
(2.4 m) above the floor in shops, offices and other sections
of the hangar where aircraft are not stored or housed.
Refer to current ANSI/NFPA No. 409, Aircraft Hangars. In
Canada, installation is suitable in aircraft hangars when
acceptable to the enforcing authorities.
Public Garages. In repair garages, duct furnaces must
be installed in a detached building or room separate from
repair areas as specified in the latest edition of NFPA 88B,
Repair Garages.
In parking structures, duct furnaces must be installed so
that the burner flames are located a minimum of 18 inches
(457 mm) above the floor or protected by a partition not
less than 18 inches (457 mm) high. Refer to the latest
edition of NFPA 88A, Parking Structures.
In Canada, installation must be in accordance with the
latest edition of CSA B149 “Installation Codes for Gas
Burning Appliances and Equipment.
NOTICE:
Equipment Damage!
Do not install duct furnaces in corrosive or flammable
atmospheres! Premature failure of, or severe damage to
the unit could result! Avoid locations where extreme
drafts can affect burner operation. Duct furnaces must
not be installed in locations where air for combustion
would contain chlorinated, halogenated or acidic
vapors. If located in such an environment, premature
failure of the unit could occur!
NOTICE:
Maintain Minimum Thermostat Setting!
Duct furnaces should not be installed to maintain low
temperatures and/or freeze protection of buildings. A
minimum of 50°F (10°C) thermostat setting must be
maintained. If duct furnaces are operated to maintain
lower than 50°F (10°C), hot flue gases are cooled inside
the heat exchanger to a point where water vapor (a flue
gas by-product) condenses onto the heat exchanger
walls. The result is a mildly corrosive acid that
prematurely corrodes the aluminized heat exchanger
and can actually drip water down from the duct furnace
onto the floor surface. Additional duct furnaces should
be installed if a minimum 50°F (10°C) thermostat
setting cannot be maintained. Failure to follow these
recommendations could result in equipment or
property damage.
WARNING
Overheating or Flooding Could Cause Fire
or Explosion!
Overheating or flooding (where any part of the duct
furnace has been under water) could result in fire or
explosion. Should overheating occur, or the gas supply
fails to shut off, shut off the manual gas valve to the
duct furnace before shutting off the electrical supply.
Do not use the duct furnace if any part has been under
water. Immediately call a qualified service technician to
inspect the duct furnace and replace any gas control
which has been underwater. Failure to follow these
recommendations could result in death or serious
injury.
WARNING
Hazardous Gases and Flammable Vapors!
Exposure to hazardous gases from fuel substances
have been shown to cause cancer, birth defects or other
reproductive harm. Improper installation, adjustment,
alteration, service or use of this product could cause
flammable mixtures. To avoid hazardous gases and
flammable vapors follow proper installation and set up
of this product and all warnings as provided in this
manual. Failure to follow all instructions could result in
death or serious injury.