SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and
servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific
knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could
result in death or serious injury. When working on the equipment, observe all precautions in the literature
and on the tags, stickers, and labels that are attached to the equipment.
UniTrane™ Fan-Coil and Force-Flo™ Air Conditioners
200 to 1,200 cfm
April 2012 UNT-SVX07D-EN
Installation, Operation,
and Maintenance
Models FC and FF
“ZO” and later design sequence
Low vertical models FCKB and FCLB
“SO” and later design sequence
UNT-SVX07_-EN.book Page 1 Friday, April 27, 2012 9:40 AM
Page view 0
1 2 3 4 5 6 ... 137 138

Summary of Contents

Page 1 - Installation, Operation

SAFETY WARNINGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating,

Page 2 - Environmental Concerns!

10 UNT-SVX07D-ENPre-InstallationReceiving and HandlingUpon delivery, inspect all components for possible shipping damage. See “Receiving Checklist” (

Page 3 - Trademarks

Startup100 UNT-SVX07D-ENTimed Override Control (UC400)If the UC400 controller has a timed override option (ON/CANCEL buttons), pushing the ON button

Page 4 - Table of Contents

StartupUNT-SVX07D-EN 101 In heating or cooling mode, the controller maintains the zone temperature based on the active heating setpoint and the active

Page 5 - UNT-SVX07D-EN 5

Startup102 UNT-SVX07D-ENsection, “Manual Fan Speed Control (UC400)”). AUTO Fan Operation; ECM Acoustical Mode (UC400)When the controller is configure

Page 6 - Model Number Descriptions

StartupUNT-SVX07D-EN 103 speed fan operation. A controller can receive a BAS-communicated outdoor air damper minimum position.A BAS-communicated minim

Page 7

Startup104 UNT-SVX07D-EN• The heating capacity is located in the reheat position• The space relative humidity is validThe space relative humidity can

Page 8

StartupUNT-SVX07D-EN 105 begins accumulating fan run time again. The diagnostics can be cleared and the filter timer reset by temporarily overriding t

Page 9

106 UNT-SVX07D-ENMaintenanceMaintenance ProceduresPerform the following maintenance procedures to ensure proper unit operation.Air FiltersChange or c

Page 10 - Pre-Installation

MaintenanceUNT-SVX07D-EN 107 Main Drain PanSee Figure 38 to replace main drain correctly.Vertical Units. To remove the main drain pan on vertical fan

Page 11 - Pre-Installation Checklist

Maintenance108 UNT-SVX07D-ENis dependent upon system operating hours, filter maintenance, and efficiency and dirt load. Follow the suggested methods

Page 12 - Dimensions and Weights

MaintenanceUNT-SVX07D-EN 109 Vertical UnitsNotes:• In vertical units, wiring to the motor transitions from the control panel onto a trough onto the fa

Page 13

Pre-InstallationUNT-SVX07D-EN 11 is continuously pitched 1 inch per 10 feet of condensate line run to adequately drain condensate.5. Wall & ceili

Page 14 - Available Models

Maintenance110 UNT-SVX07D-ENNote: Motor plug with latch.Horizontal UnitsNotes:• In horizontal units, wiring to the motor is routed below the fan boar

Page 15

MaintenanceUNT-SVX07D-EN 111 Monthly Maintenance1. Inspect unit air filters. Clean or replace if airflow is blocked or if filters are dirty.2. Check

Page 16 - Vertical Concealed, Model A

11 2 UNT-SVX07D-ENDiagnosticsOutput Testing and Diagnostics (Tracer ZN520)Translating Multiple Diagnostics (Tracer ZN520)The controller senses and re

Page 17 - Vertical Cabinet, Model B

DiagnosticsUNT-SVX07D-EN 11 3 Note: The automatic diagnostic reset function does not operate during the manual output test sequence.If a special diag

Page 18 - Horizontal Concealed, Model C

Diagnostics114 UNT-SVX07D-ENTable 39. Valves stay closed (Tracer ZN520)Probable Cause ExplanationNormal operationThe controller opens and closes the

Page 19 - Horizontal Cabinet, Model D

DiagnosticsUNT-SVX07D-EN 11 5 Output Testing and Diagnostics (UC400)This section provides information about the following:• Output testing• Diagnosti

Page 20 - Horizontal Recessed, Model E

Diagnostics11 6 UNT-SVX07D-ENManual (Latching) Diagnostics (UC400). Manual diagnostics (also referred to as latching) cause the unit to shut down. M

Page 21 - (Force-Flo Units Only)

DiagnosticsUNT-SVX07D-EN 11 7 Troubleshooting (Wireless Controls)Locations of LEDs, Test button, Test Symbols, and Error CodesThe receiver for all mo

Page 22 - Vertical Recessed, Model H

Diagnostics11 8 UNT-SVX07D-ENError codes appear on the display of the model WDS sensor when diagnostics occur (see Table 45).LED1, LED2, and LED3, lo

Page 23 - Vertical Slope Top, Model J

DiagnosticsUNT-SVX07D-EN 119 shown in Tab l e 49, p. 119 .• On model WDS, push the Test button on the sensor (see location on Figure 43, p. 117 ). I

Page 24

12 UNT-SVX07D-ENDimensions and WeightsTable 1. Fan-coil component dataUnit Size 02 03 04 06 08 10 12Coil DataFace Area — ft20.8 0.8 1.1 1.6 2.1 3.2 3

Page 25 - Low Vertical Cabinet, Model L

Diagnostics120 UNT-SVX07D-EN6. Observe the polarity indicators that are molded into the cover.7. Install two batteries (of the type specified in “Bat

Page 26

DiagnosticsUNT-SVX07D-EN 121 • The Test button on the sensor• The address test mode on the receiver• A common volt-ohm meterProcedure for Testing the

Page 27

Diagnostics122 UNT-SVX07D-ENgiven in Table 53, p. 122.Note: The output circuits are not electrically powered; consequently, resistance can be measure

Page 28 - Compact Concealed, Model P

DiagnosticsUNT-SVX07D-EN 123 If the LED is off, either the power is off, an abnormal condition is present or the TEST button is pressed.Yellow COMM LE

Page 29 - Fan-Coil Coil Connections

Diagnostics124 UNT-SVX07D-ENTroubleshooting (UC400)Tab l e 5 5 through Table 60, p. 125 provide troubleshooting information if encountering operati

Page 30 - Force-Flo Coil Connections

DiagnosticsUNT-SVX07D-EN 125 Table 58. DX or electric heat does not energize (UC400) Probable Cause ExplanationUnit wiring The wiring between the con

Page 31

Diagnostics126 UNT-SVX07D-ENTroubleshooting (ECM)Notes:• The new Trane BLDC system is a closed loop system that has equipment protections and envelop

Page 32 - Fresh Air Opening Locations

DiagnosticsUNT-SVX07D-EN 127 connections will cause malfunction and the system will shutdown.• Do not unplug or plug-in motors or connectors while the

Page 33

Diagnostics128 UNT-SVX07D-EN• Verify that the voltage jumper on the motor plug harness is absent for 208-230V units and 277V units. If the jumper is

Page 34 - Wall Box

UNT-SVX07D-EN 129 Replacing ECM ComponentsNotes:• Ensure that drip-loops are maintained on wiring on pipe end of unit to avoid wicking of water into t

Page 35 - Projection Panel

Dimensions and WeightsUNT-SVX07D-EN 13 Table 2. Low vertical fan-coil component dataUnit Size 03 04 06Coil DataFace Area — ft21.1 1.6 2.1L x D x H — i

Page 36 - Installation—Mechanical

Replacing ECM Components130 UNT-SVX07D-EN• Before assuming that any of the boards or components in the new system have failed, please ensure that the

Page 37 - Condensate Drain

Replacing ECM ComponentsUNT-SVX07D-EN 131 5. Ensure that the CSTI adapter board switches are set correctly, as indicated on the attached unit schemati

Page 38 - Venting the Hydronic Coil

132 UNT-SVX07D-ENECM Application NotesThe new Trane BLDC system has some notable differences to traditional designs.RPM ModeThe motors are programmed

Page 39

UNT-SVX07D-EN 133 Wiring DiagramsFigure 48. Unit-mounted fan speed switch with factory-mounted disconnectUNT-SVX07_-EN.book Page 133 Friday, April 2

Page 40 - Coil Damage!

Wiring Diagrams134 UNT-SVX07D-ENFigure 49. Tracer ZN 520 unit with two-stage electric heat and unit-mounted zone sensorUNT-SVX07_-EN.book Page 134

Page 41

Wiring DiagramsUNT-SVX07D-EN 135 Figure 50. CSTI unit with single-stage electric heat and unit-mounted fan switch (Note: CSTI configuration switches)U

Page 42 - Installation—General

Wiring Diagrams136 UNT-SVX07D-ENFigure 51. Tracer ZN520 unit with four-pipe configuration, condensate overflow switch and wall-mounted zone sensorUNT

Page 43 - Unit Leveling!

Wiring DiagramsUNT-SVX07D-EN 137 Figure 52. Tracer ZN510 unit with four-pipe configuration and split zone sensor/unit fan switch configurationUNT-SVX0

Page 44 - Installation Checklist

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, com

Page 45 - Installation—Controls

Dimensions and Weights14 UNT-SVX07D-ENAvailable ModelsModel A: Vertical ConcealedModel B: Vertical ShortModel C: Horizontal ConcealedModel D: Hor

Page 46

Dimensions and WeightsUNT-SVX07D-EN 15 Factory-Installed Piping PackagesNote: This figure shows piping package components and basic arrangement. It is

Page 47 - Zone Sensor Installation

Dimensions and Weights16 UNT-SVX07D-ENVertical Concealed, Model AVertical Concealed UnitUnit Size 200-300 400 600 800 1000-1200No. of Fans1122 3No. o

Page 48

Dimensions and WeightsUNT-SVX07D-EN 17 Vertical Cabinet, Model BVertical Cabinet Unit Unit Size 200-300 400 600 800 1000-1200No. of Fans1122 3No. of M

Page 49 - Installation—Electrical

Dimensions and Weights18 UNT-SVX07D-ENHorizontal Concealed, Model CHorizontal Concealed Unit Dimensions (in.) and Weights (lb)Unit Size 200-300 400 6

Page 50

Dimensions and WeightsUNT-SVX07D-EN 19 Horizontal Cabinet, Model DHorizontal Cabinet Unit Unit Size 200-300 400 600 800 1000-1200No. of Fans1122 3No.

Page 51

© 2012 Trane All rights reserved UNT-SVX07D-ENWarnings, Cautions and NoticesWarnings, Cautions and Notices. Note that warnings, cautions and notic

Page 52

Dimensions and Weights20 UNT-SVX07D-ENHorizontal Recessed, Model EHorizontal Recessed Unit Unit Size 200-300 400 600 800 1000-1200No. of Fans1122 3No

Page 53 - ECM Overview and Setup

Dimensions and WeightsUNT-SVX07D-EN 21 Vertical Wall Hung Cabinet, Model F (Force-Flo Units Only)Vertical Wall Hung Cabinet Unit Unit Size 200-300 400

Page 54 - CSTI Adapter Board

Dimensions and Weights22 UNT-SVX07D-ENVertical Recessed, Model HVertical Recessed UnitUnit Size 200-300 400 600 800 1000-1200No. of Fans1122 3No. of

Page 55 - Safety Alert!

Dimensions and WeightsUNT-SVX07D-EN 23 Vertical Slope Top, Model JVertical Slope Top UnitUnit Size 200-300 400 600 800 1000-1200No. of Fans 1 1 2 2 3N

Page 56

Dimensions and Weights24 UNT-SVX07D-ENLow Vertical Concealed, Model K 12-9/16"2-11/16"10-11/16"1-13/16"1-1/8"1-13/16"

Page 57

Dimensions and WeightsUNT-SVX07D-EN 25 Low Vertical Cabinet, Model L10-15/16"4-7/16"8-1/2"10-15/16"2-3/8"12-1/4"12-1/2&q

Page 58

Dimensions and Weights26 UNT-SVX07D-ENInverted Vertical Cabinet, Model M (Force-Flo Units Only)Inverted Vertical Cabinet Unit Dimensions (in.) and W

Page 59

Dimensions and WeightsUNT-SVX07D-EN 27 Inverted Vertical Recessed, Model N (Force-Flo Units Only)Inverted Vertical Recessed Unit Dimensions (in.) and

Page 60

Dimensions and Weights28 UNT-SVX07D-ENCompact Concealed, Model PCONTROLBOXMAIN DRAIN (OPTIONAL)CONNECTION FOR7/8” OD COPPERTUBE AND CLAMPSECONDARY DR

Page 61 - Priority / Error Display

Dimensions and WeightsUNT-SVX07D-EN 29 Fan-Coil Coil ConnectionsVertical UnitsHorizontal UnitsUNT-SVX07_-EN.book Page 29 Friday, April 27, 2012 9:4

Page 62

Warnings, Cautions and NoticesUNT-SVX07D-EN 3 Revision HistoryThe revision of this literature dated 27 Apr 2012 includes information for Tracer™ UC400

Page 63 - Configuration

Dimensions and Weights30 UNT-SVX07D-ENForce-Flo Coil ConnectionsVertical UnitsHorizontal UnitsUNT-SVX07_-EN.book Page 30 Friday, April 27, 2012 9:

Page 64 - VSP Setup Examples

Dimensions and WeightsUNT-SVX07D-EN 31 Force-Flo Coil ConnectionsInverted UnitsUNT-SVX07_-EN.book Page 31 Friday, April 27, 2012 9:40 AM

Page 65

Dimensions and Weights32 UNT-SVX07D-ENFresh Air Opening LocationsHorizontal Units—Models C, D, E, and P (Back Duct Collar Only for Model P)Fresh air

Page 66 - Adapter Board

Dimensions and WeightsUNT-SVX07D-EN 33 Fresh Air Opening LocationsVertical Units—Models A, B, F, H, J, K, L, M, and NFresh air opening dimensions, ver

Page 67

Dimensions and Weights34 UNT-SVX07D-ENWall BoxWall box dimensions Unit Size, Ref. only Dimensions A x B Internal Supports02–03 24-3/8 x 4- 3/4 104 24

Page 68

Dimensions and WeightsUNT-SVX07D-EN 35 Projection PanelProjection panel dimensions Projection panel, all unit sizes Unit Size 02–03 04 06 08 10–12A

Page 69

36 UNT-SVX07D-ENInstallation—MechanicalDuct ConnectionsInstall all air ducts according to National Fire Protection Association standards for the Inst

Page 70

Installation—MechanicalUNT-SVX07D-EN 37 Water Piping Connections to Factory-Installed Piping PackageBefore installing water piping supply and return l

Page 71

Installation—Mechanical38 UNT-SVX07D-ENAutomatic Changeover SensorTwo-pipe changeover units with either the Tracer ZN010, ZN510, ZN520, and UC400 and

Page 72

Installation—MechanicalUNT-SVX07D-EN 39 2. For units with manual air vents, back the set screw out to expel air from the unit and then re-tighten the

Page 73 - Practices

4 UNT-SVX07D-ENTable of ContentsWarnings, Cautions and Notices . . . . . . . . . . 2Model Number Descriptions . . . . . . . . . . . . . . 6Genera

Page 74 - BACnet MS/TP Link

Installation—Mechanical40 UNT-SVX07D-EN5. Adjust the circuit setter valve by turning the valve stem until the appropriate pressure drop is achieved.

Page 75 - Connection Wiring

Installation—MechanicalUNT-SVX07D-EN 41 Figure 13. Typical piping for steam coilsFigure 14. Main steam coil connection diagramCode of System Component

Page 76 - Power ON Check

42 UNT-SVX07D-ENInstallation—GeneralInstalling the UnitFollow the procedures below to install the unit properly. Refer to “Dimensions and Weights,” p

Page 77 - Wireless Sensors

Installation—GeneralUNT-SVX07D-EN 43 1. Insert the mounting bolts through the panel brackets of the trim ring and secure to the hanger holes on the un

Page 78 - Associate

Installation—General44 UNT-SVX07D-ENInstallation ChecklistThe following checklist is only an abbreviated guide to the detailed installation procedure

Page 79 - (Model WDS only)

UNT-SVX07D-EN 45 Installation—ControlsControl sensor options include both unit-mounted (factory-installed) and wall-mounted sensors. Installation inst

Page 80

Installation—Controls46 UNT-SVX07D-ENInstalling Wall-Mounted Wired SensorsReference the wall-mounted zone sensor dimensions in Figure 16, p. 46. Posi

Page 81 - Optional Features

Installation—ControlsUNT-SVX07D-EN 47 • Metal barriers between the receiver and the sensor (for example, plastered walls with metal lathe or metal roo

Page 82 - Sensor Operations

Installation—Controls48 UNT-SVX07D-EN7. To replace the cover:a. Hook the cover over the top of the back plate. Apply light pressure to the bottom of

Page 83 - Operating Mode (Model WDS)

UNT-SVX07D-EN 49 Installation—ElectricalUnit Wiring DiagramsSpecific unit wiring diagrams, based on unit options ordered, are provided inside each uni

Page 84

UNT-SVX07D-EN 5 Recommended Communication Wiring Prac-tices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73Wiring Installation (Trace

Page 85

Installation—Electrical50 UNT-SVX07D-ENRecommendation: Do not bundle or run interconnection wiring in parallel with or in the same conduit with any h

Page 86

Installation—ElectricalUNT-SVX07D-EN 51 Minimum Circuit Ampacity (MCA) and Maximum Fuse Size (MFS) Calculations for Fan-Coils with Single Phase Electr

Page 87 - Pre-Start

Installation—Electrical52 UNT-SVX07D-ENTable 12. Force-Flo single stage, low kW electric heat Unit Size Voltage# Wires kWamps/ph kWamps/ph kWamps/ph0

Page 88 - General Information

UNT-SVX07D-EN 53 ECM Overview and SetupOverviewThis addendum addresses changes to UniTrane Fan-Coil and Cabinet Heater units, integrating new Trane Br

Page 89 - ZN010 and ZN510

ECM Overview and Setup54 UNT-SVX07D-ENECM Engine Controller• The ECM engine controls and reports the performance of up to two Trane BLDC motors.• The

Page 90 - 90 UNT-SVX07D-EN

ECM Overview and SetupUNT-SVX07D-EN 55 – Standard thermostats put out only “on” signals, however customer may select a normally open valve. A selectab

Page 91 - UNT-SVX07D-EN 91

ECM Overview and Setup56 UNT-SVX07D-EN• Wall-mounted low-voltage fan speed switch inputs to the adapter boards’ terminal strips and 24 Vac tap to fie

Page 92 - Operation

ECM Overview and SetupUNT-SVX07D-EN 57 an external potentiometer or rheostat. The 10 Vdc supply supports up to 10 mA draw.TB3 (right five positions) i

Page 93 - (Tracer ZN520)

ECM Overview and Setup58 UNT-SVX07D-ENThe ECM engine board features a nested menu integrated user interface (UI) that supports:1. Status display for

Page 94 - 94 UNT-SVX07D-EN

ECM Overview and SetupUNT-SVX07D-EN 59 RPM Mode RUNNING/ FAN STATUS CONTINUOUS LOOPDisplayed when:1) No error codes are present2) Motor has completed

Page 95 - UNT-SVX07D-EN 95

6 UNT-SVX07D-ENModel Number DescriptionsUniTrane Fan-CoilFollowing is a complete description of the fan-coil model number. Each digit in the model nu

Page 96 - Binary Inputs (Tracer ZN520)

ECM Overview and Setup60 UNT-SVX07D-ENConfiguration parameter and value display and modification changesThe ECM engine board’s on-board user interfac

Page 97 - Zone Sensor (Tracer ZN520)

ECM Overview and SetupUNT-SVX07D-EN 61 Configuration Use ExamplesExample 1. To view the value of parameters without saving. In this case we wish to v

Page 98 - 98 UNT-SVX07D-EN

ECM Overview and Setup62 UNT-SVX07D-ENError CodesDisplayed during abnormal operation.Indicates a locked rotor condition of Motor 1. The motor wil

Page 99 - UC400 Sequence of Operation

ECM Overview and SetupUNT-SVX07D-EN 63 Initial Setup and ConfigurationAfter connections of power and hookup of customer installed controls/fan speed s

Page 100 - 100 UNT-SVX07D-EN

ECM Overview and Setup64 UNT-SVX07D-ENcomes standard with three to five field-accessible thermostatic inputs (with adjustable speed), so the use of t

Page 101 - Fan Operation (UC400)

ECM Overview and SetupUNT-SVX07D-EN 65 Use of Potentiometer/Rheostat For VSPA courtesy 10-Vdc supply is provided that can support a 10-mA draw. The us

Page 102 - Valve Operation (UC400)

ECM Overview and Setup66 UNT-SVX07D-ENThe ECM engine board provides additional temperature controlled logic to help coordinate certain electric-heat

Page 103 - Outdoor Air Damper (UC400)

ECM Overview and SetupUNT-SVX07D-EN 67 changeover and electric heat lockout function may not work correctly unless the ECM engine board is configured

Page 104 - 104 UNT-SVX07D-EN

ECM Overview and Setup68 UNT-SVX07D-ENb. The input impedance of the thermistor circuit must be set correctly (the  parameter should be set to 

Page 105 - Low Limit) (UC400)

ECM Overview and SetupUNT-SVX07D-EN 69 Configuration Settings of the ECM Engine BoardNote: The engine board functions and unit specific settings are s

Page 106 - Maintenance

Model Number DescriptionsUNT-SVX07D-EN 7 Digits 21, 22, 23 — Electric Heat kW — ( ) = 208V Derate000 = No Electric Heat010 = 1.0 kW (0.75 kW)015 = 1.5

Page 107 - Hazardous Chemicals!

ECM Overview and Setup70 UNT-SVX07D-ENTable 18. Configuration settings of the ECM engine board Description on Unit LabelUser Interface NameTypical Us

Page 108 - Fan Board Assembly Removal

ECM Overview and SetupUNT-SVX07D-EN 71 Mt2 Ovspd RPM Selects the rpm above which the Motor 2 will be assumed to be in an overspeed condition

Page 109 - Vertical Units

ECM Overview and Setup72 UNT-SVX07D-ENFan Speed Response Verification1. After performing controller specific commissioning, observe the display on th

Page 110 - Live Electrical Components!

UNT-SVX07D-EN 73 Wired Controllers—Communication WiringWiring Installation (ZN510 and ZN520)Tracer ZN510 and ZN520 controllers are LonTalk® devices th

Page 111 - Annual Maintenance

Wired Controllers—Communication Wiring74 UNT-SVX07D-ENWiring Overview OutlineGeneral InstructionsConformance to Regulatory StandardsAll wiring must c

Page 112 - Diagnostics

Wired Controllers—Communication WiringUNT-SVX07D-EN 75 Note: The BACnet Device ID is displayed as the Software Device ID on the Tracer TU Controller S

Page 113 - UNT-SVX07D-EN 11 3

Wired Controllers—Communication Wiring76 UNT-SVX07D-ENTransformer RecommendationsA 24Vac power supply must be used for proper operation of the binary

Page 114

Wireless SensorsUNT-SVX07D-EN 77 Wireless SensorsNote: Receivers ship installed on the unit. To remove the receiver, press in the retention tabs on th

Page 115 - Diagnostics (UC400)

Wireless Sensors78 UNT-SVX07D-ENNote: Do not use 000 as an address. An address of 000 removes all association knowledge, reverts the sensor to a low-

Page 116 - Table of Diagnostics (UC400)

Wireless SensorsUNT-SVX07D-EN 79 Configuring the Wireless Display Sensor (Model WDS only)Note: Sensors shipped with the fan-coil are pre-configured fo

Page 117 - Controls)

Model Number Descriptions8 UNT-SVX07D-ENDigit 34 0 = NoneDigit 35 — Control Function #30=None2 = Condensate Overflow DetectionDigit 36 — Control Func

Page 118

Wireless Sensors80 UNT-SVX07D-ENThe display will change to configuration mode. When the sensor is in configuration mode, a wrench symbol appears on t

Page 119

Wireless SensorsUNT-SVX07D-EN 81 4. Review the display to ensure that you have selected the correct configuration.5. To return the display to operati

Page 120 - Prevent Injury!

Wireless Sensors82 UNT-SVX07D-ENLocking or Unlocking Settings. You can lock or unlock the setpoint, system, or fan setting to prevent changes.To loc

Page 121 - (Wireless Controls)

Wireless SensorsUNT-SVX07D-EN 83 • The receiver conducts an energy scan for 20 seconds to determine the clearest channel on which to operate.• LED3 fl

Page 122

Wireless Sensors84 UNT-SVX07D-ENSome systems allow you to select both heating and cooling room temperature settings. If your system has this option,

Page 123 - ZN510, and ZN520)

Wireless SensorsUNT-SVX07D-EN 85 Testing Signal StrengthTesting Battery StatusWireless Sensor SpecificationsThe following table presents specification

Page 124 - Troubleshooting (UC400)

Wireless Sensors86 UNT-SVX07D-ENThe following table presents agency compliance information for wireless sensor set models as shown. United States com

Page 125

UNT-SVX07D-EN 87 Pre-StartPre-Startup ChecklistComplete this checklist after installing the unit to verify all recommended installation procedures are

Page 126

88 UNT-SVX07D-ENStartupTracer ZN510 and ZN520 Unit StartupRefer to the Trane publication, CNT-IOP-1 (ComfortLink 10 Controller: Installation, Operati

Page 127 - →→

StartupUNT-SVX07D-EN 89 Fan Mode Switch OperationOffFan is turned off, two-position damper option spring-returns closed.Hi, Med, LoFan runs continuous

Page 128

UNT-SVX07D-EN 9 General InformationUniTrane fan-coil and Force-Flo units are intended for single zone applications. These units have load capabilities

Page 129 - Replacing ECM Components

Startup90 UNT-SVX07D-ENIf the correct water temperature is available, the unit begins normal heating or cooling operation. If the measured entering w

Page 130 - Instructions

StartupUNT-SVX07D-EN 91 Zone Sensors (Tracer ZN010 and ZN510)The zone sensors available with the Tracer ZN010 and ZN510 provide up to three different

Page 131

Startup92 UNT-SVX07D-ENTracer ZN520 Sequence of OperationThe Tracer ZN520 operates the fan in the following modes:1. occupied2. unoccupied3. occupied

Page 132 - ECM Application Notes

StartupUNT-SVX07D-EN 93 Tracer Summit with Supply Fan Control (Tracer ZN520)If the unit is communicating with Tracer Summit and the supply fan control

Page 133 - Wiring Diagrams

Startup94 UNT-SVX07D-ENlonger. At 100 percent capacity, the heating valve is fully open (modulating valves) or on continuously (two-position valves).

Page 134

StartupUNT-SVX07D-EN 95 the local zone sensor module, a communicated request, or the default fan speed (off).If both a zone sensor module and communic

Page 135

Startup96 UNT-SVX07D-ENthe economizer enable setpoint (absolute dry bulb), the controller modulates the outdoor air damper (between the active minimu

Page 136

StartupUNT-SVX07D-EN 97 Binary Outputs (Tracer ZN520)Binary outputs are configured to support the following:• Three fan stages (when one or two fan st

Page 137

Startup98 UNT-SVX07D-ENcontroller ignores the hard-wired space temperature input and uses the communicated value. External Setpoint Adjustment (Trace

Page 138

StartupUNT-SVX07D-EN 99 UC400 Sequence of OperationThe UC400 controller will operate to maintain the space temperature setpoint. This section provides