Trane RAUJ CAUJ 20 to 120 Tons Installation Manual

Browse online or download Installation Manual for Unknown Trane RAUJ CAUJ 20 to 120 Tons. Trane RAUJ CAUJ 20 to 120 Tons Installation and Maintenance Manual User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and
servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific
knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could
result in death or serious injury. When working on the equipment, observe all precautions in the literature
and on the tags, stickers, and labels that are attached to the equipment.
Remote Air-Cooled Condensers
January 2011 CAUJ-SVX01D-EN
Installation, Operation,
and Maintenance
Models A and Later Design Sequences
CAUJ-C20 CAUJ-C40 CAUJ-C80
CAUJ-C25 CAUJ-C50 CAUJ-D10
CAUJ-C30 CAUJ-C60 CAUJ-D12
Page view 0
1 2 3 4 5 6 ... 59 60

Summary of Contents

Page 1 - Installation, Operation

SAFETY WARNINGOnly qualified personnel should install and service the equipment. The installation, starting up, andservicing of heating, ventilating,

Page 2 - CAUTIONs

10 CAUJ-SVX01D-ENDimensions and WeightsUnit ClearancesFigure 3, p. 11 and Figure 4, p. 11 illustrate the minimum operating and service clearances for

Page 3 - Trademarks

CAUJ-SVX01D-EN 11Dimensions and WeightsFigure 3. Typical installation clearances for single, multiple, or pit applications: 20-60 ton unitsFigure 4. T

Page 4 - Table of Contents

12 CAUJ-SVX01D-ENDimensions and WeightsFigure 5. 20-ton air-cooled condenser4" CONDUIT MAIN POWER1 3/4" KO LOW VOLTAGE (30V MAX.)37 11/16&qu

Page 5 - CAUJ-SVX01D-EN 5

CAUJ-SVX01D-EN 13Dimensions and WeightsFigure 6. 20-ton air-cooled condenser (connections)VOLTAGE ACCESSCONTROL PANEL7/8" O.D.LIQUID LINE8 1/16&q

Page 6 - Model Number Descriptions

14 CAUJ-SVX01D-ENDimensions and WeightsFigure 7. 25- and 30-ton air-cooled condenser1/2" X 4 KO (115V) 1 3/4" KO LOW VOLTAGE (30V MAX.)1/2&q

Page 7 - General Information

CAUJ-SVX01D-EN 15Dimensions and WeightsFigure 8. 25- and 30-ton air-cooled condenser (connections)CONTROL PANELVOLTAGE ACCESSSCALE1 .0 00SCALE1,00034

Page 8

16 CAUJ-SVX01D-ENDimensions and WeightsFigure 9. 40-ton air-cooled condenser29 1/4"31 1/4"35 13/16"37 11/16"3 3/8"3 3/8"

Page 9

CAUJ-SVX01D-EN 17Dimensions and WeightsFigure 10. 40-ton air-cooled condenser (connections)VOLTAGEACCESS1 3/8" O.D.DISCHARGELIQUID LINESCALE1,000

Page 10 - Dimensions and Weights

18 CAUJ-SVX01D-ENDimensions and WeightsFigure 11. 50-ton air-cooled condenser29 1/4"31 1/4"35 13/16"37 11/16"3 3/8"3 3/8"

Page 11

CAUJ-SVX01D-EN 19Dimensions and WeightsFigure 12. 50-ton air-cooled condenser (connections)Note List - 97075CONTROLPANELVOLTAGEACCESSSCALE1,000SCALE1,

Page 12

© 2012 Trane All rights reserved CAUJ-SVX01D-ENWarnings, Cautions and NoticesWarnings, Cautions and Notices. Note that warnings, cautions and notices

Page 13

20 CAUJ-SVX01D-ENDimensions and WeightsFigure 13. 60-ton air-cooled condenser29 1/4"31 1/4"35 13/16"37 11/16"3 3/8"3 3/8"

Page 14

CAUJ-SVX01D-EN 21Dimensions and WeightsFigure 14. 60-ton air-cooled condenser (connections)VOLTAGEACCESSCONTROLPANELSCALE1,00010 13/16"74 7/16&qu

Page 15

22 CAUJ-SVX01D-ENDimensions and WeightsFigure 15. 80-ton air-cooled condenser113/16"176 7/16"83 1/8"30 1/4"30 1/8"83 1/4"

Page 16

CAUJ-SVX01D-EN 23Dimensions and WeightsFigure 16. 80-ton air-cooled condenser (connections)VOLTAGEACCESSCONTROLPANELDISCHARGE LINECOILLIQUID LINE1 1/8

Page 17

24 CAUJ-SVX01D-ENDimensions and WeightsFigure 17. 100- and 120-ton air-cooled condenser1 15/16"108 11/16"20 1/16"5 3/16"108 5/8&qu

Page 18

CAUJ-SVX01D-EN 25Dimensions and WeightsFigure 18. 100- and 120-ton air-cooled condenser (connections)VOLTAGEAC C E S SCONTROLPANELCOILSCALE1,00075/16&

Page 19

26 CAUJ-SVX01D-ENDimensions and WeightsWeightsPoint load and isolator locationTable 2. 20 to 120 ton weights and point load dataWeight CG Locations We

Page 20

CAUJ-SVX01D-EN 27InstallationRigging and Center-of-Gravity DataA Rigging illustration and Center-of-Gravity dimensional data table is shown in Figure

Page 21

28 CAUJ-SVX01D-ENInstallationUnit IsolationTo minimize unit sound and vibration transmission, us one of the following installation methods:1. Install

Page 22

CAUJ-SVX01D-EN 29InstallationNeoprene Isolators (available for 20-60 ton units only)Install the neoprene isolators at each unit mounting (load) point,

Page 23

CAUJ-SVX01D-EN 3Warnings, Cautions and NoticesTrademarksTrane and the Trane logo are trademarks of Trane in the United States and other countries. All

Page 24 - DETAIL A

30 CAUJ-SVX01D-ENInstallationSpring Isolators (available for 20-120 ton units)Install the spring isolators at each unit mounting (load) point using th

Page 25 - DIS C H AR G E LINE

CAUJ-SVX01D-EN 31InstallationLeveling the UnitBefore tightening the mounting bolts, level the unit carefully. Use the unit base rail as a reference.Le

Page 26

32 CAUJ-SVX01D-ENInstallationField Installed Control Wiring• Verify the Control transformer (1T1) is wired for the proper operating voltage.• Install

Page 27 - Installation

CAUJ-SVX01D-EN 33InstallationLiquid Line ComponentsFilter driers and valves (expansion valves, charging valves, etc.) should be provided in the liquid

Page 28 - Unit Isolation

34 CAUJ-SVX01D-ENInstallationTable 6. Valve selectionsApplicable UnitsCapacityBleed Selection Minimum Maximum0Any BPHE or any Fin and Tube OK CoilsBBI

Page 29

CAUJ-SVX01D-EN 35InstallationDischarge (Hot Gas) LinesDischarge lines should be pitched downward 1/2 inch for each 10 feet of horizontal run in thedir

Page 30

36 CAUJ-SVX01D-ENInstallationFinal Refrigerant Pipe ConnectionsTo access the refrigerant pipe connections, remove the louvered side grills. Refer to F

Page 31 - General Unit Requirements

CAUJ-SVX01D-EN 37InstallationLeak Testing ProcedureWhen Leak-testing a refrigerant system, observe all safety precautions.Trane condensing units are s

Page 32 - Refrigerant Piping

38 CAUJ-SVX01D-ENInstallationField Installed Power WiringAn overall dimensional layouts for the field installed wiring entrance into the unit are illu

Page 33 - Equipment Damage!

CAUJ-SVX01D-EN 39InstallationTable 8. Customer connection wire range: 20-60 ton unitsCustomer wire selection and fuse replacementPower Wire Selection

Page 34

4 CAUJ-SVX01D-ENTable of ContentsModel Number Descriptions ... 6General Information ...

Page 35 - 7/8" 470 2-1/8" 750

40 CAUJ-SVX01D-ENInstallationPower Wire Sizing and Protection Device EquationsTo correctly size the main power wiring for the unit, use the appropriat

Page 36

CAUJ-SVX01D-EN 41InstallationField Installed Control WiringBefore installing any connecting wiring, refer to Figure 5, p. 12 through Figure 18, p. 25

Page 37 - Hazard of Explosion!

42 CAUJ-SVX01D-ENInstallationElectrical DataTable 10. Electrical dataUnit Characteristics Condenser Fan MotorNominalTons Model No.ElectricalCharacteri

Page 38 - Field Installed Power Wiring

CAUJ-SVX01D-EN 43Operating PrincipalsStandard air cooled condensers function as the outdoor condensing units for appropriately sizedsplit refrigeratio

Page 39

44 CAUJ-SVX01D-ENOperating Principals80-120 Ton SpecsCondenser fan cycling is accomplished through interlocking the fan operation with compressoropera

Page 40 - Calculation #2

CAUJ-SVX01D-EN 45System Pre-Start ProceduresUse the checklist provided below in conjunction with the “General Unit Requirement” checklist” toensure th

Page 41 - Hazardous Voltage!

46 CAUJ-SVX01D-ENSystem Pre-Start ProceduresThe lines used to connect the pump to the system should be copper and of the largest diameterthat can prac

Page 42 - Electrical Data

CAUJ-SVX01D-EN 47System Pre-Start ProceduresFigure 25. Typical vacuum pump hookupFigure 26. Evacuation time vs. pressure rise2004006008001000120014001

Page 43 - Operating Principals

48 CAUJ-SVX01D-ENSystem Pre-Start ProceduresVoltage ImbalanceExcessive three phase voltage imbalance between phases will cause motors to overheat ande

Page 44 - 80-120 Ton Specs

CAUJ-SVX01D-EN 49Start-UpLow Ambient Damper OperationLow Ambient Dampers are available as a factory installed option or can be field-installed. Damper

Page 45 - System Pre-Start Procedures

CAUJ-SVX01D-EN 5Service and Maintenance ... 54Fuse Replacement Data ...

Page 46 - Standing Vacuum Test

50 CAUJ-SVX01D-ENStart-Upapproximately 73º F. The second stage opens when the ambient temperature approaches 45º F andcloses at approximately 53º F.Ve

Page 47

CAUJ-SVX01D-EN 51Start-UpNote: Interchanging “Load” side power wires at the fan contactors will only affect the individualfan rotation. Ensure that th

Page 48 - Switch 1S1!

52 CAUJ-SVX01D-ENStart-UpTo check damper operation, jumper between the sensor input terminals 6 and 7 and/or 11 and 12(if applicable). Controller outp

Page 49 - Start-Up

CAUJ-SVX01D-EN 53Start-UpC30 12 19C40 11 24C50 12 25C60 13 32C80 29 47D10 30 50D12 33 63Notes: 1. CAUJ-C20 - C30 are single-circuit units; CAUJ-40 - C

Page 50 - Rotating Components!

54 CAUJ-SVX01D-ENService and MaintenanceFuse Replacement DataFall Restraint - Condenser Section RoofThis unit is built with fall restraint slots locat

Page 51 - Live Electrical Components!

CAUJ-SVX01D-EN 55Service and MaintenanceMonthly MaintenanceAir Handling EquipmentBefore completing the following checks, turn the system control circu

Page 52 - C25 12 19

56 CAUJ-SVX01D-ENService and Maintenance• Inspect the condenser coils for dirt and foreign debris. If the coils appear dirty, clean themaccording to t

Page 53

CAUJ-SVX01D-EN 57Service and MaintenanceTo clean refrigerant coils, use a soft brush and a sprayer.Note: DO NOT use detergents with microchannel conde

Page 54 - Service and Maintenance

58 CAUJ-SVX01D-ENWarranty and Liability ClauseCOMMERCIAL EQUIPMENT RATED 20 TONS AND LARGER AND RELATEDACCESSORIESPRODUCTS COVERED - This warranty* is

Page 55 - Monthly Maintenance

CAUJ-SVX01D-EN 59Wiring DiagramsNote: For easier access, published unit wiring diagrams (individual, separate diagrams for unitaryproduct lines) will

Page 56 - Coil Cleaners!

6 CAUJ-SVX01D-EN20 to 60 TonDigit 1 — Unit TypeC = CondenserDigit 2 — CondenserA = Air-CooledDigit 3 — AirflowU = UpflowDigit 4 — DevelopmentSequenceJ

Page 57 - No Step Surface!

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, theleader in creating and sustaining safe, comf

Page 58 - Warranty and Liability Clause

CAUJ-SVX01D-EN 7General InformationUnit InspectionAs soon as the unit arrives at the job site• Verify nameplate data matches data on sales order and b

Page 59 - Wiring Diagrams

8 CAUJ-SVX01D-ENGeneral InformationThe unit control panel contains all required fan cycling controls, compressor interlocks, and a 115 volt control p

Page 60

CAUJ-SVX01D-EN 9General InformationTable 1. General data20 Ton 25 Ton 30 Ton 40 Ton 50 Ton 60 Ton 80 Ton 100 Ton 120 TonModel Number CAUJC-20 CAUJC-25