Mechanical Specifications
BTUs/lb. less than the return air enthalpy. During occupied mode, the outside air damper opens to
15% (adjustable 0-100%) for ventilation purposes. Also, the ability to alter the outside air damper
position to compensate for VAV supply air modulation is inherent in the unit controls, and can be
enabled by the operator. An analog 2-10VDC output (adjustable (0-10VDC) is provided to modulate
the field-provided 30-second damper actuators (adjustable 1-255 seconds).
Basic Water Piping
This option is available on units without a waterside economizer and with condenser water
applications above 54°F that do not require condensing pressure control. Left hand water
connections and piping are extended to the unit exterior. Manifold piping is factory installed.
Intermediate Water Piping
This option provides condensing temperature control when the unit is configured (user defined at
the HI) for variable water flow with or without a waterside economizer. A two-way modulating
control valve is wired and installed in the unit to maintains a specific range of water temperature
rise through the condenser when entering fluid temperature is less than 58°F.This option allows
the compressor to operate with entering fluid temperature down to 35°F.The minimum valve
position to maintain minimum condenser flow rates is user-defined at the human interface.This
valve drives closed if the unit shuts down or if a power failure occurs.
Waterside Economizer Flow Control
Units equipped with a waterside economizer can be set from the human interface panel for variable
or constant water flow.
Constant Water Flow
Two-way modulating control shutoff valves are wired, controlled, and installed in the unit. One
valve is located in the economizer’s water inlet, and the other is in the condenser bypass water inlet.
When the waterside economizer enables, the two-way valves modulate to maintain the discharge
air temperature setpoint. As the economizer valve opens, the condenser bypass valve closes, and
vice versa. Full water flow is always maintained through the condensers. Both valves will close in
the event of a power failure.
Variable Water Flow
Two-way modulating control shutoff valves are wired, controlled, and installed in the unit. One
valve is located in the economizer’s water inlet, and the other is in the condenser bypass water inlet.
When the economizer valve is active, the condenser bypass valve closes.The economizer valve
modulates, thus water flow through the unit is modulates. If the water is cool enough for
economizing, but mechanical cooling is also required, the economizer valve fully opens to establish
full water flow through the condensers.Whenever the water is too warm for economizing and there
is a call for cooling, the economizer valve fully closes and the bypass valve fully opens, establishing
full water flow through the condensers. Full water flow is always maintained through the
condensers when mechanical cooling is required. Both valves close whenever cooling is not
required, and in the event of a power failure.
Water Flow Switch
A water flow switch is factory installed in the condenser water pipe within the unit. Whenever the
flow switch detects a water flow loss prior to or during mechanical cooling, compressor operation
locks out and a diagnostic code displays. If water flow is restored, the compressor operation
automatically restores.
Service Valves
Service valves are factory installed on each circuit before and after the compressor to allow
compressor isolation for servicing.