Trane Modular 20 to 35 Tons Parts List Page 45

  • Download
  • Add to my manuals
  • Print
  • Page
    / 88
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 44
PKG-PRC003U-EN 45
Controls
STATUS is used to monitor all temperatures, pressures, humidities, setpoints, input and output
status.
CUSTOM allows the user to customize a status report, which can consist of up to four screens
of data available in the main STATUS menu.
SETPOINT is used to edit all factory preset default setpoints.
DIAGNOSTICS allows the user to review active and historical lists of diagnostic conditions. A
total of 49 different diagnostics can be read at the human interface (HI) panel and the last 20
diagnostics can be held in an active history buffer log at the HI panel.
SETUP allows the user to edit control parameters, sensor selections, setpoint source selections,
output definitions, and numerous other points in this menu. All points have factory preset
values to keep unnecessary editing to a minimum.
CONFIGURATION allows changing of factory-preset unit configuration information.This
information can be edited only if certain options are field-installed or deleted from the unit. For
example, if aTracer LCI-I communication interface module or ventilation override module
(VOM) were field-installed, the unit configuration will require editing to reflect those options for
proper unit operation.
SERVICE allows servicing or troubleshooting the unit by selecting component control outputs
such as compressors, fans, damper position, etc.This menu is accessible only at the unit-
mounted human interface panel.
Control Sequences of Operation
Morning Warmup
This feature is available on all types of factory-installed heat units and on units with no heat.This
function may still be selected to support systems with heat sources not provided by the self-
contained unit. At the conclusion of unoccupied mode, the selected zone is heated to the user-
defined morning warmup setpoint.The unit is then released to occupied mode.There are two types
of morning warmup: full capacity or cycling capacity.
Full Capacity Morning Warmup (MWU)
Full capacity morning warmup uses full heating capacity to heat the zone as quickly as possible.
Full heating capacity is provided until the morning warmup setpoint is met. At this point, the unit
is released to daytime mode.
Cycling Capacity Morning Warmup (MWU)
Cycling capacity morning warmup provides a more gradual heating to overcome “building sink”
as the zone is heated. Normal zone temperature control with varying capacity is used to raise the
zone temperature to the MWU zone temperature setpoint.This method of warmup is used to
overcome the “building sink” effect. Cycling capacity MWU will operate until MWU setpoint is
reached or for 60 minutes.Then the unit switches to occupied mode. Cooling will suspend until
building load conditions exceed the MWU setpoint of 3°F (1.7°C), which is field adjustable.
Note: When using the morning warmup option in a VAV heating/cooling self-contained unit,
airflow must be maintained through the self-contained unit.This can be accomplished by
electrically tying the VAV boxes to the unoccupied output relay contacts on the unit’s RTM
module or by using changeover thermostats. Either of these methods will assure adequate
airflow through the unit and satisfactory heating.
Ventilation Override (VOM)
The user can customize up to five different override sequences (A-E) for purposes of ventilation
override control. If more than oneVOM sequence is being requested, the sequence with the highest
priority is initiated first. Priority schedule is that sequence A (unit off) is first, with sequence “E”
(purge with duct pressure control) last.
Page view 44
1 2 ... 40 41 42 43 44 45 46 47 48 49 50 ... 87 88

Comments to this Manuals

No comments