Mechanical Specifications
operating efficiency. An outside air temperature and relative humidity sensor are provided to allow
monitoring of reference enthalpy and are field installed. Economizer operation enables when the
outside air enthalpy is less than 25 BTUs/lb. default (adjustable 19-28 BTUs/lb.). During occupied
mode, the outside air damper opens to 15% (adjustable 0-100%) for ventilation purposes. Also, the
ability to alter the outside air damper position to compensate for VAV supply air modulation is
inherent in the unit controls, and can be enabled by the operator.
The mixing box fabrication is galvanized steel. Opposed low leak damper blades are galvanized
steel and rotate on rustproof nylon bushings. A factory installed 24V modulating spring return
actuator controls both damper positions.
Comparative Enthalpy Control
Units with comparative enthalpy control are equipped with the necessary control sequences to
allow using outside air for the first stage of cooling, in occupied or unoccupied mode and when
ambient conditions are favorable for economizing. Inherent in the unit controller is the ability to
suppress the setpoint below the normal unit setpoint.This allows the building to improve comfort
levels when possible, and at the same time, optimize building mechanical cooling operation for
peak operating efficiency. A factory-installed control board, with field-installed outside and return
air temperature and relative humidity sensors, allows monitoring of outside and return air.
Economizer operation enables when the outside air enthalpy is 3 BTUs/lb. less than the return air
enthalpy. During occupied mode, the outside air damper opens to 15% (adjustable 0-100%) for
ventilation purposes. Also, the ability to alter the outside air damper position to compensate for
VAV supply air modulation is inherent in the unit controls, and can be enabled by the operator.
The mixing box fabrication is galvanized steel. Opposed low leak damper blades are fabricated
from galvanized steel and rotate on rustproof nylon bushings. A factory installed 24V modulating
spring return actuator controls both damper positions.
StandardTwo-Position Damper Interface
Units with the two-position damper interface are provided with a 0-10 VDC control output suitable
for controlling a field-provided modulating actuator. In occupied mode, the output drives to the
maximum position.
Airside Economizer Interface
Units with airside economizer interface are equipped with the necessary control sequences to
allow using outside air for the first stage of cooling, in occupied or unoccupied mode and when
ambient conditions are favorable for economizing. Inherent in the unit controller is the ability to
suppress the setpoint below the normal unit setpoint.This allows the building to improve comfort
levels when possible, and at the same time, optimize building mechanical cooling operation for
peak operating efficiency. An outside air temperature and relative humidity sensor are provided for
field installation to monitor reference enthalpy. Economizer operation enables when the outside
air enthalpy is less than 25 BTUs/lb. (adjustable 19-28 BTUs/lb.). During occupied mode, the outside
air damper opens to 15% (adjustable 0-100%) for ventilation purposes. Also, the ability to alter the
outside air damper position to compensate for VAV supply air modulation is inherent in the unit
controls, and can be enabled by the operator. An analog 2-10 VDC output (adjustable (0-10 VDC)
is provided to modulate the field-provided 30 second damper actuators (adjustable 1-255 seconds).
Airside Economizer Interface with Comparative Enthalpy
Units with airside economizer interface and comparative enthalpy are equipped with the necessary
control sequences to allow using outside air for the first stage of cooling, in occupied or unoccupied
mode and when ambient conditions are favorable for economizing. Inherent in the unit controller
is the ability to suppress the setpoint below the normal unit setpoint.This allows the building to
improve comfort levels when possible, and at the same time, optimize building mechanical cooling
operation for peak operating efficiency. A factory-installed control board, with outside and return
air temperature and relative humidity sensors, are provided for monitoring outside and return air.
The sensors are field installed. Economizer operation enables when the outside air enthalpy is 3