VAV-PRC011M-EN 37
Single-Duct VAV Terminal Units
Table 24. Heating capacity (kW) - inlet size 16x24 (SI)
Water
Pressure
Drop (kPa)
Airflow (L/s)
Rows L/s 378 566 849 1133 1416 1699 1982 2265 2548 2831 3115 3398 3775
1-Row
Capacity
kW
0.13 4.11 11.61 13.70 16.00 17.71 19.06 20.16 21.08 21.85 22.52 23.09 23.60 24.05 24.58
0.19 8.50 12.69 15.14 18.09 20.44 22.36 23.98 25.36 26.57 27.63 28.57 29.40 30.16 31.05
0.25 14.27 13.29 16.04 19.31 22.07 24.38 26.38 28.12 29.66 31.03 32.26 33.38 34.39 35.61
0.32 21.39 13.69 16.63 20.18 23.15 25.75 28.02 30.03 31.83 33.44 34.91 36.25 37.47 38.96
0.38 29.81 13.96 17.04 20.81 23.97 26.74 29.22 31.44 33.43 35.24 36.89 38.41 39.81 41.52
0.44 39.50 14.16 17.34 21.27 24.60 27.50 30.13 32.51 34.66 36.63 38.44 40.10 41.65 43.54
0.50 50.42 14.32 17.58 21.64 25.09 28.13 30.85 33.35 35.64 37.74 39.67 41.46 43.12 45.17
2-Row
Capacity
kW
0.32 3.40 20.03 25.22 30.47 34.03 36.63 38.61 40.19 41.48 42.55 43.47 44.25 44.94 45.73
0.44 6.41 20.96 26.88 33.14 37.57 40.89 43.49 45.59 47.33 48.81 50.07 51.17 52.14 53.27
0.57 10.31 21.50 27.87 34.79 39.80 43.63 46.68 49.17 51.26 53.04 54.57 55.92 57.11 58.51
0.69 15.10 21.85 28.52 35.90 41.33 45.54 48.92 51.71 54.07 56.08 57.84 59.38 60.75 62.36
0.82 20.76 22.10 28.99 36.71 42.46 46.95 50.59 53.61 56.17 58.38 60.31 62.01 63.52 65.31
0.95 27.28 22.29 29.34 37.32 43.32 48.04 51.88 55.09 57.82 60.18 62.24 64.07 65.71 67.63
1.07 34.65 22.43 29.62 37.80 43.99 48.90 52.91 56.27 59.13 61.62 63.80 65.74 67.47 69.52
1.20 42.87 22.55 29.84 38.18 44.54 49.60 53.74 57.23 60.21 62.81 65.09 67.11 68.93 71.08
1.33 51.94 22.64 30.02 38.50 44.99 50.18 54.44 58.03 61.12 63.80 66.16 68.26 70.15 72.39
1.45 61.84 22.72 30.17 38.77 45.38 50.66 55.03 58.71 61.88 64.64 67.08 69.25 71.20 73.51
3-Row
Capacity
kW
0.32 4.23 22.77 29.21 35.82 40.30 43.55 46.03 47.98 49.56 50.88 51.99 52.95 53.78 54.73
0.44 7.89 23.70 31.01 38.91 44.54 48.78 52.09 54.77 56.98 58.84 60.43 61.82 63.03 64.43
0.57 12.62 24.22 32.06 40.78 47.18 52.10 56.03 59.24 61.93 64.22 66.20 67.92 69.45 71.23
0.69 18.37 24.55 32.74 42.02 48.97 54.40 58.78 62.40 65.46 68.08 70.36 72.36 74.14 76.22
0.82 25.15 24.79 33.21 42.91 50.26 56.07 60.80 64.74 68.09 70.97 73.49 75.72 77.70 80.04
0.95 32.92 24.96 33.57 43.57 51.24 57.35 62.35 66.55 70.13 73.23 75.95 78.35 80.50 83.04
0.95 32.92 24.96 33.57 43.57 51.24 57.35 62.35 66.55 70.13 73.23 75.95 78.35 80.50 83.04
1.20 51.44 25.20 34.06 44.51 52.63 59.17 64.58 69.15 73.09 76.51 79.53 82.21 84.62 87.48
1.33 62.17 25.28 34.24 44.85 53.14 59.84 65.41 70.13 74.19 77.74 80.88 83.67 86.18 89.17
1.45 73.87 25.35 34.39 45.13 53.56 60.40 66.10 70.94 75.13 78.78 82.02 84.91 87.51 90.60
4-Row
Capacity
kW
0.32 5.06 25.52 33.38 41.46 46.88 50.74 53.62 55.86 57.65 59.13 60.35 61.39 62.29 63.31
0.44 9.39 26.44 35.37 45.16 52.15 57.37 61.41 64.64 67.28 69.49 71.36 72.97 74.38 75.99
0.57 14.93 26.93 36.48 47.34 55.38 61.57 66.47 70.46 73.78 76.58 78.99 81.08 82.92 85.04
0.69 21.66 27.24 37.19 48.77 57.55 64.44 69.99 74.56 78.41 81.70 84.54 87.02 89.22 91.78
0.82 29.55 27.46 37.68 49.77 59.10 66.52 72.56 77.60 81.87 85.54 88.73 91.54 94.03 96.96
0.95 38.58 27.61 38.04 50.52 60.27 68.09 74.53 79.93 84.54 88.52 92.01 95.08 97.83 101.05
1.07 48.75 27.73 38.31 51.09 61.17 69.33 76.08 81.78 86.67 90.91 94.63 97.94 100.89 104.37
1.20 60.03 27.82 38.53 51.55 61.89 70.32 77.34 83.28 88.40 92.86 96.79 100.28 103.41 107.11
1.33 72.42 27.89 38.70 51.92 62.48 71.14 78.37 84.53 89.84 94.48 98.59 102.24 105.52 109.42
1.45 85.91 27.96 38.85 52.23 62.98 71.82 79.24 85.57 91.05 95.86 100.11 103.90 107.32 111.38
Note: Refer to the Hot Water Reheat & Coil Notes (SI) at the end of the Performance Data section for fouling factors and LAT/WTD calculating equations.