24 GHND-SVX01C-EN
Installation: Electrical
Electrical Connections
Standard units are shipped for use on 115 volt, 60 hertz
single phase electric power. The motor nameplate and
electrical rating of the transformer should be checked
before energizing the unit heater electrical system. All
external wiring must conform to the latest edition of ANSI/
NFPA No. 70 National Electrical Code and applicable local
codes; in Canada, to the Canadian Electrical Code, Part 1
CSA Standard C22.1.
It is recommended that the electrical power supply to each
unit heater be provided by a separate, fused, and
permanently live electrical circuit. A disconnect switch of
suitable electrical rating for each unit heater should be
located as close to the gas valve and controls as possible.
Each unit heater must be electrically grounded in
accordance with the latest edition of the National Electric
Code, ANSI/NFPA No. 70 or CSA Standard C22.1.
The transformer supplied with this unit heater is internally
fused. Any overload or short circuit will ruin the
transformer.
Thermostat Wiring and Location
Note: The thermostat must be mounted on a vertical,
vibration-free surface, free from air currents, and in
accordance with the furnished instructions.
Mount the thermostat approximately 5 feet (1.5 m) above
the floor in an area where it will be exposed to a free
circulation of average temperature air. Always refer to the
thermostat instructions as well as our unit wiring diagram,
and wire accordingly. Avoid mounting the thermostat in
the following locations:
1. Cold areas—Outside walls or areas where drafts may
affect the operation of the control.
2. Hot areas—Areas where the sun’s rays, radiation, or
warm air currents may affect control operation.
3. Dead areas—Areas where air cannot circulate freely,
suc
h as behind doors or in corners.
Note: Thermostat wires tagged “W” and “G” must be
connected together except when using a general
purpose “SPDT” 24 Vac relay and a standard
thermostat with subbase, or when using
Honeywell T834H or T834 thermostats. Also refer
to Figure 19, p. 24 for other wiring connections.
Thermostat Heat Anticipator Adjustments. The
initial heat anticipator setpoint should equal the
thermostat’s current amperage draw when the unit is
firing. This setpoint should be measured for the best
results. Use the recommended ranges as a guide. If further
information is needed, consult your thermostat
manufacturers instructions.
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures
recommended in this section of the manual could result
in exposure to electrical, mechanical or other potential
safety hazards. Always refer to the safety warnings
provided throughout this manual concerning these
procedures. When possible, disconnect all electrical
power including remote disconnect and discharge all
energy storing devices such as capacitors before
servicing. Follow proper lockout/tagout procedures to
ensure the power can not be inadvertently energized.
When necessary to work with live electrical
components, have a qualified licensed electrician or
other individual who has been trained in handling live
electrical components perform these tasks. Failure to
follow all of the recommended safety warnings
provided, could result in death or serious injury.
WARNING
Hazardous Voltage and Gas!
Turn off the gas supply and disconnect all electric
power, including remote disconnects before servicing
unit. Follow proper lockout/tagout procedures to
ensure the power can not be inadvertently energized
and the gas can not be inadvertently turned on. Failure
to turn off gas or disconnect power before servicing
could result in death or serious injury.
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE & ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow these requirements could result in death or
serious injury.