10 GHND-SVX01C-EN
Unit Dimensions and Weights
Table 1. Performance and dimensional data: Power Vented Propeller Unit Heater
Unit Size 100 125 150 175 200 225 250 300 350 400
PERFORMANCE DATA
(a)
Input BTU/Hr 100,000 125,000 150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000
(kW) (29.3) (36.6) (43.9) (51.2) (58.6) (65.9) (73.2) (87.8) (102.5) (117.1)
Output BTU/Hr 80,000 100,000 120,000 140,000 160,000 180,000 200,000 240,000 280,000 320,000
(kW) (23.4) (29.3) (35.1) (41.0) (46.9) (52.7) (58.6) (70.3) (82.0) (93.7)
Thermal Efficiency %80808080808080808080
Free Air Delivery CFM cfm 1,480 1,650 2,200 2,530 2,640 2,700 3,100 4,400 5,000 5,300
(m
3
/s) (0.699) (0.779) (1.038) (1.194) (1.246) (1.274) (1.463) (2.077) (2.360) (2.502)
Air Temperature Rise °F 50 56 50 51 56 61 60 50 52 56
(°C) (28) (31) (28) (28) (31) (34) (33) (28) (29) (31)
Outlet Velocity fpm 775 910 1,045 1,070 1,010 950 980 1,100 1,150 1,050
(m/s) (3.94) (4.62) (5.31) (5.44) (5.13) (4.83) (4.98) (5.59) (5.84) (5.33)
Full Load Amps at 115V 5.2 7.2 7.8 9.2 9.2 9.2 9.2 12.5 15.0 15.0
MOTOR DATA:
Motor hp 1/20 1/10 1/4 1/3 1/3 1/3 1/3 1/4 1/3 1/3
(kW) (0.037) (0.075) (0.186) (0.249) (0.249) (0.249) (0.249) (0.186) (0.249) (0.249)
Type SP SP PSC PSC PSC PSC PSC PSC PSC PSC
RPM 1,050 1,050 1,140 1,140 1,140 1,140 1,140 1,140 1,140 1,140
Amps @ 115V 2.6 4.2 4.7 5.8 5.8 5.8 5.8 9.4 11.6 11.6
DIMENSIONAL DATA
A” Height to Top of Unit
in. 31-1/4 31-1/4 36-1/4 36-1/4 36-1/4 36-1/4 36-1/4 36-1/4 36-1/4 36-1/4
(mm) (794) (794) (921) (921) (921) (921) (921) (921) (921) (921)
“B” Width of Unit in. 17-7/8 20-5/8 20-5/8 23-3/8 26-1/8 28-7/8 31-5/8 37-1/8 42-5/8 48-1/8
(mm) (454) (524) (524) (594) (664) (733) (803) (943) (1083) (1222)
“C” Height to Top of Hanger
in. 34-1/8 34-1/8 39-1/8 39-1/8 39-1/8 39-1/8 39-1/8 39-1/8 39-1/8 39-1/8
(mm) (867) (867) (994) (994) (994) (994) (994) (994) (994) (994)
“D” Depth to Rear of Housing
in. 37-1/2 37-1/2 37-1/2 37-1/2 37-1/2 37-1/2 37-1/2 37-1/2 37-1/2 37-1/2
(mm) (952) (952) (952) (952) (952) (952) (952) (952) (952) (952)
“E” Hanging Distance Width
in. 14-1/2 17-1/4 17-1/4 20 22-3/4 25-1/2 28-1/4 33-3/4 39-1/4 44-3/4
(mm) (368) (438) (438) (508) (578) (648) (718) (857) (997) (1137)
“F” Discharge Opening Width
in. 15-3/8 18-1/8 18-1/8 20-7/8 23-5/8 26-3/8 29-1/8 34-5/8 40-1/8 45-5/8
(mm) (391) (460) (460) (530) (600) (670) (740) (879) (1019) (1159)
“G” Depth to Unit Side Jacket
in. 26-3/4 26-3/4 26-3/4 26-3/4 26-3/4 26-3/4 26-3/4 26-3/4 26-3/4 26-3/4
(mm) (679) (679) (679) (679) (679) (679) (679) (679) (679) (679)
“H” Discharge Opening Height
in.18181818181818181818
(mm) (457) (457) (457) (457) (457) (457) (457) (457) (457) (457)
“J” to Centerline of Flue in. 5-7/8 7-1/4 7-1/4 8-5/8 10 11-1/4 12-3/4 15-1/2 18-1/4 21
(mm) (149) (184) (184) (219) (254) (286) (324) (394) (464) (533)
“K” Depth to Centerline of Flue
in. 30-5/8 30-5/8 30-5/8 30-5/8 30-5/8 30-5/8 30-5/8 30-5/8 30-5/8 30-5/8
(mm) (778) (778) (778) (778) (778) (778) (778) (778) (778) (778)
“L” Hanger Location in. 16-1/4 16-3/4 16-3/8 16-3/8 16-3/8 16-3/4 16-3/4 16-3/4 16-3/4 16-3/4
(mm) (413) (425) (416) (416) (416) (425) (425) (425) (425) (425)
Flue Size Dia. in.*4444555666
(mm) (102) (102) (102) (102) (127) (127) (127) (152) (152) (152)
Fan Diameter in.14161618181818(2) 16(2) 18(2) 18
Gas Inlet-Natural Gas in. 100,000 125,000 150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000
Gas Inlet-LP Gas in. 1/2 1/2 1/2 1/2 1/2
1/2 or 3/4
Approx. Shipping Wt. lb 174 197 219 238 249 275 305 350 414 461
(kg) (79) (89) (99) (108) (113) (125) (138) (159) (188) (209)
Notes:
1. For installations in Canada, any references to deration at altitudes in excess of 2000 ft. (610m) are to be ignored. At altitudes of 2000 to 4500 ft.
(610m to 1372m), the unit must be derated to 90% of the normal altitude rating, and be so marked in accordance with the ETL certification.
2. Legend: SPH = SPLIT PHASE, CAP. START = CAPACITOR START
(a) Ratings shown are for unit installations at elevations between 0 and 2000 ft. (610 m). For unit installations in USA above 2000 ft. (610 m), the unit
input must be derated 4% for each 1000 ft. (305 m) above sea level; refer to local codes, or in absence of local codes, refer to the latest edition of the
National Gas Code, ANSI Standard Z223.1 (N.F.P.A. No. 54).
** Refer to corresponding ** in Figure 6, p. 11.