SSAAFFEETTYY WWAARRNNIINNGG
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and
air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered
equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the
literature and on the tags, stickers, and labels that are attached to the equipment.
March 2015
SSA-SVX06E-EN
Split System Air Conditioners
Odyssey
Air Handler 5 to 25 Tons
MMooddeell ((6600 HHzz))
TWE061D/E***A
TWE090D/E**BA
TWE120D/E**BA
TWE150E**BA
TWE180E**BA
TWE240E**BA
TWE300E**BA
MMooddeell ((5500 HHzz))
TWE051D***A
TWE076D/E***A
TWE101D/E***A
TWE126E***A
TWE156E***A
TWE201E***A
TWE251E***A
Installation, Operation,
and Maintenance
Page view 0
1 2 3 4 5 6 ... 47 48

Summary of Contents

Page 1 - Installation, Operation

SSAAFFEETTYY WWAARRNNIINNGGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating,

Page 2 - Introduction

10SSA-SVX06E-ENFigure 4. Evaporator coil reorientation for TWE126,150, 156, 180Top bracket screwsRotate 4°clockwisePreparation for Refrigerant PipingN

Page 3 - Revision History

SSA-SVX06E-EN11Dimensional DataFigure 5. Height, width and depth measurementsHDWModel NumberH - in. (mm) W - in. (mm) D - in. (mm)TWE051, 061 48-1/8 (

Page 4 - Table of Contents

12SSA-SVX06E-ENFigure 6. 4.6, 5 ton air handler, single circuit3" (76.2)48 1/16"(1220. 8)10 7/16"(265. 1)34 9/16"(877. 9)35 5/8&qu

Page 5 - Model Number Description

SSA-SVX06E-EN13Figure 7. 5 ton air handler, dual circuit3" (76.2)48 1/16"(1220. 8)10 7/16"(265. 1)34 9/16" (877. 9)35 5/8"(90

Page 6 - General Information

14SSA-SVX06E-ENFigure 8. 6.25, 7.5 ton air handler, single circuit16 7/8"(428.6)1 13/16"(46)2 3/4"(69.85)42"(1066.8)1 9/16"(3

Page 7 - Pre-Installation

SSA-SVX06E-EN15Figure 9. 6.25, 7.5 ton air handler, dual circuit16 7/8"(406.4)1 13/16"(46)2 3/4"(69.9)42"(1066.8)1 9/16"(39.7

Page 8 - NNOOTTIICCEE

16SSA-SVX06E-ENFigure 10. 8.33, 10 ton air handler, single circuit3 1/2" (89)8 7/8"(225. 4)16 1/16"(408)1 3/16"(30.2)22 7/8"(

Page 9 - Refrigerant Piping

SSA-SVX06E-EN17Figure 11. 8.33, 10 ton air handler, dual circuit3 1/2" (89)8 7/8"(225. 4)16 1/16"(408)1 3/16"(30.2)22 7/8"(58

Page 10 - Recommendations

18SSA-SVX06E-ENFigure 12. 10.4, 13, 12.5, 15 ton air handler, dual circuit19 1/2" (495.3)74 1/8"(1882.8)3 7/16" (87.3)2 3/4"(69.8)

Page 11 - Dimensional Data

SSA-SVX06E-EN19Figure 13. 16.7, 20.9, 20, 25 ton air handler, dual circuit20 15/16"(531.8)2 15/16"(74.6)4 3/4"(120.6)83 1/8"(2111.

Page 12 - SSA-SVX06E-EN

©2015 Trane All rights reservedSSA-SVX06E-ENIntroductionRead this manual thoroughly before operating orservicing this unit.Warnings, Cautions, and Not

Page 13

20SSA-SVX06E-ENWeightsAir HandlerTable 1. Standard air handler (TWE) — unit and corner weights - (60 Hz)TonsModelNumberShippingMax (lbs)Net Max(lbs)Co

Page 14

SSA-SVX06E-EN21Figure 15. Vertical — TWE126, 156, 201, 251, 150, 180, 240, 300Top ViewControl Box AccessFigure 16. Horizontal — TWE051, 076, 101, 061,

Page 15

22SSA-SVX06E-ENInstallationHorizontal SuspensionIf the air handler will be suspended, use a suspensionmounting kit to isolate the unit from the struct

Page 16

SSA-SVX06E-EN23WWAARRNNIINNGGFFiibbeerrggllaassss WWooooll!!YYoouu MMUUSSTT wweeaarr aallll nneecceessssaarryy PPeerrssoonnaall PPrrootteeccttiivveeEE

Page 17

24SSA-SVX06E-ENTo replace filters from the end of the unit, remove loweraccess panel (either end) and slide old filters out andreplace with new ones.T

Page 18

SSA-SVX06E-EN25Table 4. SZVAV air handler speed to voltage(continued)Parameter 6-15 Set to 60 HzHigh Speed(Hz)TP1(RTOM)Voltage(Vdc)High Speed(Hz)TP1(R

Page 19

26SSA-SVX06E-ENTable 7. Minimum supply fan speeds for 2-Speed units(continued)FunctionFan Output %Cool 2 (C1 + C2 Energized)100%CV Staged Heat100%(a)F

Page 20 - Air Handler

SSA-SVX06E-EN27EDC Switch WiringEElleeccttrroommeecchhaanniiccaall UUnniittss: To enable the EvaporatorDefrost Control Switch remove the "W3"

Page 21 - WWeeiigghhttss

28SSA-SVX06E-ENTable 9. DA heat setpoint (continued)Voltage(Vdc)Setpoint(ºF)Voltage(Vdc)Setpoint(ºF)Voltage(Vdc)Setpoint(ºF)Voltage(Vdc)Setpoint(ºF)0.

Page 22 - Installation

SSA-SVX06E-EN29Inspect fan assembly to insure all moving partsmove freely.If unit is horizontally mounted, make suresecondary drain pan has been insta

Page 23 - Condensate Piping

SSA-SVX06E-EN3WWAARRNNIINNGGRReeffrriiggeerraanntt uunnddeerr HHiigghh PPrreessssuurree!!SSyysstteemm ccoonnttaaiinnss ooiill aanndd rreeffrriiggeerra

Page 24 - Air Flow Settings

30SSA-SVX06E-ENFigure 26. ReliaTel jobsite connectionsNSB P anelZo ne SensorT’s ta tAir HandlerDisconnect S witch(By Others)Disconnect S witch(By Oth

Page 25 - Minimum Supply Fan Output

SSA-SVX06E-EN31Electrical Data60 Hz ModelsIncludes Standard, SZVAV and 2–Speed VFD airhandlers.Table 11. Voltage operating range (all air handlers)Mod

Page 26 - Setpoints

32SSA-SVX06E-ENTable 12. Electrical characteristics — standard and low static motors — 60 Hz standard air handler (continued)TonsUnitModel NumberStand

Page 27 - EDC Switch Wiring

SSA-SVX06E-EN33Table 13. Electrical characteristics — high and ultra-high static motors — 60 Hz standard air handler (continued)TonsUnitModel NumberHi

Page 28 - Installation Checklist

34SSA-SVX06E-ENTable 15. Unit wiring with electric heat (single point connection) — 5-25 ton standard air handlers — 60 HzTonsUsed WithHeater ModelNum

Page 29 - Connections

SSA-SVX06E-EN35Table 15. Unit wiring with electric heat (single point connection) — 5-25 ton standard air handlers — 60 Hz(continued)Tons Used WithHea

Page 30 - IInnssttaallllaattiioonn

36SSA-SVX06E-ENTable 15. Unit wiring with electric heat (single point connection) — 5-25 ton standard air handlers — 60 Hz(continued)Tons Used WithHea

Page 31 - Electrical Data

SSA-SVX06E-EN37Table 16. Unit wiring with electric heat (single point connection) — 7.5-25 ton SZVAV and 2-Speed VFD air handlers —60 Hz (continued)To

Page 32 - EElleeccttrriiccaall DDaattaa

38SSA-SVX06E-ENTable 16. Unit wiring with electric heat (single point connection) — 7.5-25 ton SZVAV and 2-Speed VFD air handlers —60 Hz (continued)To

Page 33

SSA-SVX06E-EN39Table 16. Unit wiring with electric heat (single point connection) — 7.5-25 ton SZVAV and 2-Speed VFD air handlers —60 Hz (continued)To

Page 34

4SSA-SVX06E-ENModel Number Description. . . . . . . . . . . . . . . . . 5Air Handler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Gen

Page 35

40SSA-SVX06E-EN50 Hz ModelsIncludes standard air handlersTable 17. Electrical characteristics — standard motor — 50 Hz air handlerTons Unit Model Numb

Page 36

SSA-SVX06E-EN41Table 19. Unit wiring with electric heat (single point connection) — air handlers (continued)BAYHTRL405* 5TWE101DD,TWE101ED1 14 15BAYHT

Page 37

42SSA-SVX06E-ENStart-UpSequence of OperationNNOOTTIICCEEEEqquuiippmmeenntt DDaammaaggee!!EEnnssuurree tthhee ddiissccoonnnneecctt ffoorr tthhee iinndd

Page 38

SSA-SVX06E-EN43capacity will be reduced in order to maintain thecalculated discharge air setpoint.Cooling Stages Minimum Fan SpeedAs the unit begins t

Page 39

44SSA-SVX06E-ENMaintenancePerform all of the indicated maintenance procedures atthe intervals scheduled. This will prolong the life of theunit and red

Page 40 - 50 Hz Models

SSA-SVX06E-EN45WWAARRNNIINNGGHHaazzaarrddoouuss VVoollttaaggee ww//CCaappaacciittoorrss!!DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iin

Page 41

46SSA-SVX06E-ENMaintenance LogDateAmbientTemp.(°F)Evaporator Entering Air CompressorSuperheat (°F)(at compressor)Subcooling (°F)(at service valve)DryB

Page 42 - Start-Up

SSA-SVX06E-EN47Wiring Diagram MatrixTable 21. Wiring schematics for TWE air handlersElectromechanical(Sd)Electromechanical(2 speed)ReliatelModel No. T

Page 43 - 2–Speed VFD Applications

Table 21. Wiring schematics for TWE air handlers (continued)Electromechanical(Sd)Electromechanical(2 speed)ReliatelModel No. TonCircuit Volts HzPhSche

Page 44 - Maintenance

SSA-SVX06E-EN5Model Number DescriptionAir HandlerT WE 2 40 E D 0 0 * *1 2 3 4 5 6 7 8 9 10 11 12T WE 201 E D 0 0 * *1 2 3 4 5 6 7 8 9 10 11 12NNoottee

Page 45 - Coil Cleaning

6SSA-SVX06E-ENGeneral InformationThis manual describes proper installation, operation,and maintenance procedures for air cooled systems. Bycarefully r

Page 46 - Maintenance Log

SSA-SVX06E-EN7Pre-InstallationThe final position for the air handler must be dictatedby required service access to it, weight distributionover structu

Page 47 - Wiring Diagram Matrix

8SSA-SVX06E-ENa. Slide the drain pan into the openingb. Lift the drain pan upc. Push it in all the wayd. Drop it down over the lip of the opening, sec

Page 48 - 02 Mar 2015

SSA-SVX06E-EN9Field Conversion to 460 VoltWWAARRNNIINNGGHHaazzaarrddoouuss VVoollttaaggee ww//CCaappaacciittoorrss!!DDiissccoonnnneecctt aallll eellee