SAFETY WARNINGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing ofheating, ventilating,
Dimensions and Weights10 WSHP-SVX10B-ENFigure 2. GET 009-036Table 2. GET 009-036GET A B C D E F009, 01216¼"(413)16¼"(413)8 1/8"(206)39
Dimensions and WeightsWSHP-SVX10B-EN 11Return Air (hinged) Acoustical DoorThe hinged acoustical door is recessed into the wall so thatthe door is flus
12 WSHP-SVX10B-ENInstallationGeneral Installation ChecksThe checklist below is a summary of the steps required tosuccessfully install a unit.This chec
InstallationWSHP-SVX10B-EN 13If unit cabinet assembly includes factory provided risers,and "no" field provided between-the-floor riserextens
Installation14 WSHP-SVX10B-ENMain Unit Power WiringA field supplied disconnect switch must be installed at ornear the unit in accordance with the Nati
InstallationWSHP-SVX10B-EN 153. Locate dimensions A and B for sheet rock opening size.The position of the sheet rock opening must becentered side-to-s
Installation16 WSHP-SVX10B-ENChassis Installation(a) Not all units will include shipping bolts.4. Connect water coil pipe to the system riser with afl
InstallationWSHP-SVX10B-EN 17may have occurred due to increased heat. Repair asrequired.5. Open the system at the lowest point for the initial blowdow
Installation18 WSHP-SVX10B-ENPSC Blower Motor Speed RetrofitPSC motors installed in the unit have multiple speedconfigurations.To modify the rpm of th
InstallationWSHP-SVX10B-EN 19Table 10. PSC blower motor external static pressure without return air door (RAD) with filterExternal Static Pressure (in
© 2013Trane All rights reserved WSHP-SVX10B-ENWarnings, Cautions and NoticesWarnings, Cautions and Notices. Note that warnings,cautions and notices ap
Installation20 WSHP-SVX10B-ENTable 11. ECM Blower motor external static pressure without return air door (RAD) with filterModel No.Speed ProfileExtern
WSHP-SVX10B-EN 21Electrical DataTable 13. Electrical performanceModel No.Motor Option Unit VoltsTotal FLAComp RLA (ea)Comp LRABlower Motor FLABlower M
22 WSHP-SVX10B-ENPre-Start-upChecklistBefore energizing the unit, the followingsystem devices must be checked:____ Is the high voltage power supply co
WSHP-SVX10B-EN 23Operating PressuresUse the form on p. 26 to log system and unit temperaturesduring start-up.GENERAL:There are many variables (airflow
Operating Pressures24 WSHP-SVX10B-ENGETE015 75 2.80 148-171 272-346 12-15 17-21 167-192 328-417 10-12 29-37GETE015 75 3.80 148-171 261-332 9-11 17-22
Operating PressuresWSHP-SVX10B-EN 25Water Pressure DropTable 15, p. 25 should be used to define feet of head/pressure drop.Note: To calculate feet of
26 WSHP-SVX10B-ENStart-upInstalling Contractor: Use this form to thoroughly check-out the system and units before and during start-up. (Thisform need
WSHP-SVX10B-EN 27MaintenancePreventive MaintenanceMaintenance on the unit is simplified with the followingpreventive suggestions:Filter maintenance mu
28 WSHP-SVX10B-ENTroubleshootingPreliminary Trouble Inspection• If operational difficulties are encountered, be sure toperform the preliminary checks
TroubleshootingWSHP-SVX10B-EN 29Table 20. Troubleshooting checklistProblem Heating Cooling Cause CorrectionNo response to any thermostat settingX X Ma
Warnings, Cautions and NoticesWSHP-SVX10B-EN 3Revision SummaryWSHP-SVX10B-EN (15 November 2013)• WPRD Chassis Model Number changeWSHP-SVX10B-EN (18 Ju
30 WSHP-SVX10B-ENUnit WiringFigure 17. Tracer ZN510/1 Ph1K1464847454441434240393837363534333231302919242827262523222120181716151413121110897652431DESC
Unit WiringWSHP-SVX10B-EN 31Figure 18. Deluxe 230V/60 Hz/1 Ph1K146484745444143424039383736353433323130291924282726252322212018171615141312111089765243
Unit Wiring32 WSHP-SVX10B-ENFigure 19. Tracer ZN510/1 Ph with ECM motor1K14648474544414342403938373635343332313029192428272625232221201817161514131211
Unit WiringWSHP-SVX10B-EN 33Figure 20. Deluxe 24V/1 Ph with ECM motor1K1464847454441434240393837363534333231302919242827262523222120181716151413121110
34 WSHP-SVX10B-ENWarrantyStandard WarrantyThe standard water-source heat pump warranty isTrane’sparts-only warranty, running 12-months from startup, n
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader increating and sustaining safe, comf
4 WSHP-SVX10B-ENTable of ContentsModel Number Descriptions ... 5General Information ... 7Pre-Installation ...
WSHP-SVX10B-EN 5Vertical High-Rise CabinetWSHPDigits 1-3: Unit ConfigurationGET = High Efficiency Vertical High RiseHeat PumpDigit 4: Development Sequ
6 WSHP-SVX10B-ENModel Number DescriptionsDigit 34, 35, 36: Riser Length000 = No Riser096 = 96" Riser Length097 = 97" Riser Length098 = 98&qu
WSHP-SVX10B-EN 7General InformationBlower/MotorThe blower and motor is located inside the unit cabinet.The blower and motor may be removed from the ca
8 WSHP-SVX10B-ENPre-InstallationJobsite InspectionAlways perform the following checks before accepting aunit:1. Verify that the nameplate data matches
WSHP-SVX10B-EN 9Dimensions and WeightsUnit Location and ClearancesLocate the unit in an indoor area.The ambienttemperature surrounding the unit must n