CLCH-PRC024A-EN 53
Controls
Figure 66. Field-installed discharge air
sensor for use with electric heat.
Model number digit 31 = A, B, C, D
Discharge air sensor.
Discharge air sensor is field-installed when using electric heat.
Figure 67. Damper actuator for mixing
section
Model Number Digit 31 = C or D
Damper actuator.
This damper actuator uses a 0–10 Vdc signal and is factory-wired and
mounted to the damper assembly. It allows zero to 100 percent fresh air.
The damper will drive open to an adjustable minimum stop-position
whenever the fan is running during occupied mode and will spring-return
closed when the fan turns off.
Trane recommends using the low temperature detection option with
fresh air dampers to detect possible freeze conditions.
Figure 68. Miscellaneous end devices
Optional end devices include (clockwise L-R): discharge air sensor (digit
31=A, B, C, D), duct static pressure transducer (digit 32=B), condensate
overflow switch (digit 30=1), and fan status switch (digit 30=1).