Voyager™ I Rooftop Units
Cooling-only TSD/TSH 060 072 102 120
Reversible WSD/WSH 060 072 090
Gas-fired YSD/YSH 060 072 090 102 120
Installation
Operation
Maintenance
RT-SVX20A-E4
Page view 0
1 2 ... 68

Summary of Contents

Page 1 - Maintenance

Voyager™ I Rooftop UnitsCooling-only TSD/TSH 060 072 102 120Reversible WSD/WSH 060 072 090Gas-fired YSD/YSH 060 072 090 102 120InstallationOperationMa

Page 2 - General information

InstallationRT-SVX20A-E410Installing the unit on the groundTo install the unit on the ground, itsbase must be level and supportedsecurely. For horizon

Page 3

Installation11RT-SVX20A-E4Table 4 - Duct dimensions for downflow units (mm)Table 5 - Duct dimensions for downflow units (mm)Unit size ABCDTSH/WSH 0605

Page 4 - Contents

InstallationRT-SVX20A-E412Condensate drain pipingA 3/4" condensate drain connectionwith P-trap is provided. Follow localcodes and standard piping

Page 5

Installation13RT-SVX20A-E4Gas pipework installationThe installation must conform to allstandards and regulations.The gas supply pipework and gasstop v

Page 6

InstallationRT-SVX20A-E414Filter installationTo gain access to filters, remove thesupply fan access panel ondownflow units and the filter accesspanel

Page 7

Installation15RT-SVX20A-E4To adjust beltThe fan belts must be inspectedperiodically to assure proper unitoperation. Replacement isnecessary if the bel

Page 8

Component air pressure dropsTable 9 - Pressure drop through accessoriesUnitsizeAirflow(m3/h)FilterEU2/G2FilterEU4/G4Economizer100% outside airElectric

Page 9

Installation17RT-SVX20A-E4Standard driveOversize driveNote : Data includes pressure drops for standard filters and wet coilsTable 10 - TSD 060 Availab

Page 10

InstallationRT-SVX20A-E418Standard driveOversize driveNote : Data includes pressure drops for standard filters and wet coilsTable 12 - TSD 072 Availab

Page 11

Installation19RT-SVX20A-E4Standard driveOversize driveNote : Data includes pressure drops for standard filters and wet coilsTable 14 - TSD 090 Availab

Page 12

General informationRT-SVX20A-E42ForewordThese instructions are given as aguide to good practice in theinstallation, start-up, operation, andmaintenanc

Page 13

InstallationRT-SVX20A-E420Standard driveOversize driveNote : Data includes pressure drops for standard filters and wet coilsTable 16 - TSD 102 Availab

Page 14

Installation21RT-SVX20A-E4Standard driveOversize driveNote : Data includes pressure drops for standard filters and wet coilsTable 18 - TSD 120 Availab

Page 15

InstallationRT-SVX20A-E422Standard driveOversize driveNote : Data includes pressure drops for standard filters and wet coilsStandard driveOversize dri

Page 16

Installation23RT-SVX20A-E4Standard driveOversize driveNote : Data includes pressure drops for standard filters and wet coilsStandard driveOversize dri

Page 17

InstallationRT-SVX20A-E424Standard driveOversize driveNote : Data includes pressure drops for standard filters and wet coilsStandard driveOversize dri

Page 18

Installation25RT-SVX20A-E4Standard driveOversize driveNote : Data includes pressure drops for standard filters and wet coilsStandard driveOversize dri

Page 19

InstallationRT-SVX20A-E426Standard driveOversize driveNote : Data includes pressure drops for standard filters and wet coilsTable 28 - YSD 120 Availab

Page 20

Installation27RT-SVX20A-E4Standard driveOversize driveNote : Data includes pressure drops for standard filters and wet coilsTable 30 - WSD 060 Availab

Page 21

InstallationRT-SVX20A-E428Standard driveOversize driveNote : Data includes pressure drops for standard filters and wet coilsStandard driveOversize dri

Page 22

Installation29RT-SVX20A-E4Standard driveOversize driveNote : Data includes pressure drops for standard filters and wet coilsStandard driveOversize dri

Page 23

General information3RT-SVX20A-E4ReceptionOn arrival, inspect the unit beforesigning the delivery note. In case ofvisible damage: The consignee (orthe

Page 24

InstallationRT-SVX20A-E430Electrical connectionThe electric panel is located in theunit compressor section. Removethe compressor access panel. Theunit

Page 25

Installation31RT-SVX20A-E4The "ABC" indicator on the face ofthe phase indicator will glow ifphase is ABC for terminals L1, L2,L3.IMPORTANT!

Page 26

InstallationRT-SVX20A-E432Table 37 - Compressor and condenser motorsTable 38 - Supply fan motorStandard supply fan motor Oversized supply fan motor U

Page 27

Controls33RT-SVX20A-E4Control wiringThe control circuit is 24 V AC. Unitincludes a 400/24 V transformer.WARNING!The unit disconnectswitch must be open

Page 28

ControlsRT-SVX20A-E434Trane THS01,THS02, THP01 andTHP02 Thermostats are directlyconnected to RTRM board(J7 connector). Trane THS03 and THP03 thermo

Page 29

Controls35RT-SVX20A-E4The CO2 sensor is designed tooperate with a nominal 24 Vacsupply. The power supply shouldmaintain the voltage between 20 to26 Va

Page 30

ControlsRT-SVX20A-E436Wiring the wall-mounted CO2sensorDVC setpoint potentiometer oneconomizer module can be adjustedas follows:0% - 500ppm, 50% - 100

Page 31

Controls37RT-SVX20A-E4Mounting the wall-mounted sensor1. Select a proper location in theroom to mount the CO2 sensor.Look for an interior wall withgoo

Page 32

ControlsRT-SVX20A-E438Mounting the duct-mounted CO2sensor1. Select a proper location on theduct to mount the CO2 sensor.2. Drill a 22-25 mm hole in

Page 33 - Controls

Controls39RT-SVX20A-E4Remote potentiometerTo install the remote potentiometer,cut the jumper WL on theeconomizer ECA board, and connectthe wires to J1

Page 34

ContentsRT-SVX20A-E44General information 2Foreword 2Warnings and Cautions 2Reception 3Warranty 3Refrigerant 3Maintenance contract 3Storage 3Training 3

Page 35 - 2 + 2% of

ControlsRT-SVX20A-E440Fire thermostatThere are two sensors in the firethermostat Kit: Sensor X13100040-01 is factory-set to open at 57°C,Sensor X13100

Page 36

Controls41RT-SVX20A-E4Clogged filter detectorThis device is mounted in theindoor fan section. The sensormeasures the difference in pressurebefore and

Page 37

ControlsRT-SVX20A-E442Thermostats6 thermostats are available:THS01/THP01, THS02/THP02 andTHS03/THP03."THS" are non programmablethermostats,

Page 38

Controls43RT-SVX20A-E4Other accessories availableRemote temperature sensor to beused with THS/THP 01-02.TZS01: Remote room temperaturesensor to be use

Page 39

Unit OptionsRT-SVX20A-E444Hot water coil(Down flow units only)In order to prevent water to freezeup in the coil during unoccupiedperiod or shutdown li

Page 40

Unit Options45RT-SVX20A-E4Electric HeaterElectric heaters are fitted on the fandischarge.Heaters have two heating stagesand provided with two types of

Page 41

Unit OptionsRT-SVX20A-E4460 - 25% fresh air hoodThe 0-25% fresh air hood allows tointroduce fresh air into the unit.This is a manual device fitted on

Page 42 - X X X X - X

Unit Options47RT-SVX20A-E4Barometric reliefThe barometric relief allows tominimize overpressure in thebuilding caused by the introductionof fresh air.

Page 43

OperationRT-SVX20A-E448Operation with aconventional thermostatThe ReliaTel module hasconventional thermostatconnections as well as Zone SensorModule c

Page 44 - Unit Options

Operation49RT-SVX20A-E4Logic is also provided to causeappropriate unit functions wheninappropriate thermostat signals areprovided. Simultaneous calls

Page 45 - Soft Starter

Contents5RT-SVX20A-E4Unit Options 44Hot water coil 44Electric Heater 45Soft Starter 450 - 25% fresh air hood 46Barometric relief 47Operation 48Op

Page 46 - 0 - 25% fresh air hood

OperationRT-SVX20A-E450Unoccupied modeIf the thermostat being used isprogrammable, it will have its ownstrategy for unoccupied mode andwill control th

Page 47 - Barometric relief

Operation51RT-SVX20A-E4To check the damper is functioningcorrectly, the ECA is equipped withan indicator light in the middle ofthe board. This light o

Page 48 - Operation with a

OperationRT-SVX20A-E452Test proceduresOperating checklist before start-up• Unit is level, with sufficientclearance all round• Duct network is correctl

Page 49

Operation53RT-SVX20A-E4Test modesThere are 2 methods in which the"Test" mode can be cycled with thetest button:1. Step Test Mode This metho

Page 50

OperationRT-SVX20A-E454Unit start-upVerification of gas valve settings -(Reserved for the qualified gastechnician)WARNING! Improper gas valvesetting m

Page 51 - 2 Sensor

Operation55RT-SVX20A-E4Starting the unit in cooling modeBefore start-up, ensure that allpower cables are tightened.Verify that the unit airflow rate i

Page 52

OperationRT-SVX20A-E456ReliaTel™ is a microelectroniccontrol feature, which providesoperating functions that aresignificantly different fromconvention

Page 53

Operation57RT-SVX20A-E4Low Ambient OperationDuring low ambient operation,outside air temperature below 13ºC,the RTRM will cycle the compressorand outd

Page 54 - Unit start-up

OperationRT-SVX20A-E458Economizer Set-UpAdjusting the minimum positionpotentiometer located on the uniteconomizer Actuator (ECA) sets therequired amou

Page 55

Operation59RT-SVX20A-E4Refer to the ignition control modulediagnostics section for the LEDdiagnostic definitions.When the fan selection switch is sett

Page 56

InstallationRT-SVX20A-E46General information:Theinstallation must conform to alllocal standards and regulations.Reception of unitsRooftop unitThere ar

Page 57

MaintenanceRT-SVX20A-E460To keep the unit operating safelyand efficiently, the manufacturerrecommends that a qualified servicetechnician check the ent

Page 58

Maintenance61RT-SVX20A-E4Note: Do not attempt to cleandisposable filters. Permanent filterscan be cleaned by washing with amild detergent and water. E

Page 59

MaintenanceRT-SVX20A-E462TroubleshootingThe RTRM has the ability to providethe service personnel with someunit diagnostics and system statusinformatio

Page 60

Maintenance63RT-SVX20A-E4Below is the complete listing offailure indication causes:System failureCheck the voltage betweenterminals 6 and 9 on J6, it

Page 61

MaintenanceRT-SVX20A-E464Service FailureMeasure the voltage betweenterminals J6-10 & J6-6. Clogged Filter = Approximately32 VDC.Normal = Less than

Page 62

Maintenance65RT-SVX20A-E4Zone Temperature Sensor (ZTS) Test Note:These procedures are not forprogrammable or digital modelsand are conducted with the

Page 63

MaintenanceRT-SVX20A-E466To Test Humidity SensorsReturn Air Humidity Sensor ECA RAH/RAEOutdoor Humidity Sensor ECA OAH/OAETo test this circuit, place

Page 64

Notes67RT-SVX20A-E4

Page 65

Literature Order Number RT-SVX20A-E4Date 0606Supersedes RT-SVX20A-E4_1105Literature Stocking Location EuropeTrane has a policy of continuous product a

Page 66

Installation7RT-SVX20A-E4Dimensions/Weights/ClearancesThe structure accommodating theunit(s) must be designed to supportthe equipment in operation, as

Page 67 - 67RT-SVX20A-E4

InstallationRT-SVX20A-E48Figure 4ABCDCenter ofgravity width Center ofgravity length Center ofgravity Table 3 - Factory-installed options and accessori

Page 68 - Supersedes RT-SVX20A-E4_1105

Installation9RT-SVX20A-E4Installing the unitDischarge ConversionIf a unit is to be converted toVertical discharge, a panel must beacquired from Trane.