Trane 1-Way Cassette-Indoor Installation Manual

Browse online or download Installation Manual for Split-system air conditioners Trane 1-Way Cassette-Indoor. Trane 1-Way Cassette-Indoor Installation and Maintenance Manual User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 40
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and
servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific
knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could
result in death or serious injury. When working on the equipment, observe all precautions in the literature
and on the tags, stickers, and labels that are attached to the equipment.
February 2013 VRF-SVX27A-EN
Installation, Operation,
and Maintenance
Variable Refrigerant Flow System
1-Way Cassette Indoor Unit Series
Models: 4TVE0007B100NB, 4TVE0009B100NB, 4TVE0012B100NB
DB68-03799A(1)
Page view 0
1 2 3 4 5 6 ... 39 40

Summary of Contents

Page 1 - Installation, Operation

SAFETY WARNINGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating,

Page 2 - Introduction

10 VRF-SVX27A-ENInstallation7. Tighten the nuts to suspend the unit following the guidelines in the figure below. 8. Maintain proper spacing between

Page 3 - Table of Contents

VRF-SVX27A-EN 11InstallationInstalling Refrigerant PipingConnect field-supplied piping using flared connections (not supplied) or by brazing. The larg

Page 4 - 4 VRF-SVX27A-EN

12 VRF-SVX27A-ENInstallation1. Slide the flare nut over the pipe to be flared.2. Slide the end of the pipe into the hole on the flaring bar that fits

Page 5 - Model Number Description

VRF-SVX27A-EN 13Installation6. Align the pipes and tighten the flare nuts manually and then with a spanner torque wrench, applying the torque accordin

Page 6 - Preparing for Installation

14 VRF-SVX27A-ENInstallation3. Disconnect refrigerant cylinder. Connect dry nitrogen cylinder to high side charging port and increase pressure to 150

Page 7 - Unit Dimensions

VRF-SVX27A-EN 15InstallationInstalling the Drain SystemInstall the drain hose as follows: 1. Push the supplied drain hose as far as possible over the

Page 8 - Service Clearances

16 VRF-SVX27A-ENInstallation• The hose should not be allowed to hang loose from its connection to the unit. Fasten the hose to a wall, frame or other

Page 9

VRF-SVX27A-EN 17Installation1. Operate the unit in cool mode.2. Remove drain pump cover.3. Squirt water into the drain pan (see figure).4. Confirm tha

Page 10 - Purging the Unit

18 VRF-SVX27A-ENInsulationInsulationAfter determining that there are no leaks in the refrigerant pipes or drainage hose, insulate them as described i

Page 11 - Installing Refrigerant Piping

VRF-SVX27A-EN 19Wiring the UnitWiring the UnitObserve the following precautions when making electrical connections. • Make all electrical connections

Page 12 - Installation

© 2013 Trane All rights reserved VRF-SVX27A-ENIntroductionRead this manual thoroughly before operating or servicing this unit.Warnings, Cautions, a

Page 13 - Leak Testing Pipe Connections

20 VRF-SVX27A-ENWiring the UnitFigure 1. Wiring diagramFigure 2. Conduit bracket installation 1(L)2(N) F2F1 1(L)1(L)2(N)2(N)F1F1F2F2F4F3F3 F4208–

Page 14

VRF-SVX27A-EN 21ConfigurationConfigurationAll VRF indoor units are factory configured. If modifications are required, one of the following control dev

Page 15 - Installing the Drain System

22 VRF-SVX27A-ENConfigurationFigure 3. VRF Wireless Remote ControlMode buttonFan upTemp upTemp downFan downPower button2-digit segment

Page 16 - Testing the Drainage

VRF-SVX27A-EN 23ConfigurationThe 2-Digit SegmentsEach 2-digit segment is differentiated from the others by a combination of operation mode and timer o

Page 17

24 VRF-SVX27A-ENConfigurationMode 2: Option SettingWhen digit 2 is set to a value of “2,” the options shown in Table 1 can be set to the values in th

Page 18 - Insulation

VRF-SVX27A-EN 25Configuration14 External control0: Disabled1: On/Off control2: Off-only control15 External control output0: Thermostat control1: User

Page 19 - Wiring the Unit

26 VRF-SVX27A-ENConfigurationMode 5: Option SettingWhen digit 2 is set to a value of “5,” the options shown in Table 2 can be changed to the values i

Page 20

VRF-SVX27A-EN 27ConfigurationFigure 6. Heat recovery unit operating in auto-changeover mode9Time required for mode changeNote: Applies only when digit

Page 21 - Configuration

28 VRF-SVX27A-ENConfigurationMode A: AddressingWhen digit 2 is set to a value of “A,” unit address settings can be changed. See Figure 7, Figure 8, a

Page 22

VRF-SVX27A-EN 29ConfigurationMode d: Specific Digit ChangingWhen digit 2 is set to a value of “d,” a single, specific digit can be changed. See Figure

Page 23 - Configuration Modes

Table of ContentsVRF-SVX27A-EN 3Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 24 - Mode 2: Option Setting

30 VRF-SVX27A-ENConfigurationFigure 10. Example of using the specific digit changing mode to change an option settingThe example in Figure 11 shows h

Page 25

VRF-SVX27A-EN 31ConfigurationTable 4. Specific digit changing mode: Digit 2 = dDisplay screen (Mode and On/Off)DigitOption Set digit to...1 Factory se

Page 26 - Mode 5: Option Setting

32 VRF-SVX27A-ENOperationOperationFamiliarize yourself with the unit components and operating tips before operating the unit.ComponentsNote: Your uni

Page 27

VRF-SVX27A-EN 33OperationInternal ProtectionsInternal protections operate if an internal fault occurs in the unit. Note: If the heat pump is operating

Page 28 - Mode A: Addressing

34 VRF-SVX27A-ENOperation2. Remove the air filter by lifting it upwards while pushing slightly and then pulling it forward. 3. Detach the grill by un

Page 29

VRF-SVX27A-EN 35Operation(b)These operations must always be performed by qualified personnel. For more detailed information, see the installation manu

Page 30

36 VRF-SVX27A-ENTroubleshootingTroubleshootingRefer to Table 6 for solutions to common problems and to Table 7 for a list of alarm conditions with co

Page 31

VRF-SVX27A-EN 37TroubleshootingIf an error occurs, one of more of the LEDs on the display (see “Components” for their location) will flicker. As a pro

Page 32 - Operation

38 VRF-SVX27A-ENTroubleshootingCondenser mid-sensor is looseloose E241Off Off Flickering Flickering FlickeringRefrigerant leakage (2nd detection) E55

Page 33 - Cleaning the Exterior

VRF-SVX27A-EN 39Warranty For Trane Advantage™ VRF Systems and Related AccessoriesWarranty For Trane Advantage™ VRF Systems and Related AccessoriesProd

Page 34 - Periodic Maintenance Checks

4 VRF-SVX27A-ENOperating Ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33Operating Mode f

Page 35

The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustainin

Page 36 - Troubleshooting

VRF-SVX27A-EN 5Model Number DescriptionDigit 1: RefrigerantDigit 2: Brand name Digit 3: System typeDigit 4: Configuration Type (also see separate t

Page 37

6 VRF-SVX27A-ENPreparing for InstallationPreparing for InstallationAccessoriesIn addition to product literature, the following accessories are suppli

Page 38

VRF-SVX27A-EN 7Preparing for InstallationUnit DimensionsUnit: inch (mm)40-3/16 (970)45-1/4 (1150): Ceiling openingDrain hole16-1/8 (410)19-11/16 (500)

Page 39 - Related Accessories

8 VRF-SVX27A-ENPreparing for InstallationService Clearances59 (1500)59 (1500)59 (1500)59 (1500)

Page 40

VRF-SVX27A-EN 9InstallationInstallationReview “Installation Considerations” before proceeding with installation.Follow the procedures in these section

Comments to this Manuals

No comments